2015-05-20 09:33:23ELECTRICAL PROVISO:
 BECAUSE THIS IS AN ADDITION TO AN EXISTING SYSTEM, IT
 IS ASSUMED THAT ALL REQUIRED DEVICES SUBORDINATE TO
 THIS INSTALLATION AND THE SURROUNDING AREAS THOUGH NOT
 INDICATED ON THE DRAWINGS AS EXISTING ARE IN PLACE. ANY
 MISSING DEVICES WILL HAVE TO BE ADDED FOR FINAL
 INSPECTION AND INCLUDED IN AN AS-BUILT DRAWING WHICH IS
 TO BE APPROVED BY THE CITY OF WEST PALM BEACH.
 A RE-ACCEPTANCE TEST REPORT AS REQUIRED BY NFPA 72
 SECTION 14.4.2 SHALL BE PROVIDED FOR FIRE & ELECTRICAL
 INSPECTORS AND INCLUDED IN THE SYSTEM LOG BOOK.
  