Plan Review Notes
Plan Review Notes For Permit 15040783
Permit Number 15040783
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-20 09:20:26ELECTRICAL PROVISO:
 BECAUSE THIS IS AN ADDITION TO AN EXISTING SYSTEM, IT
 IS ASSUMED THAT ALL REQUIRED DEVICES SUBORDINATE TO
 THIS INSTALLATION AND THE SURROUNDING AREAS THOUGH NOT
 INDICATED ON THE DRAWINGS AS EXISTING ARE IN PLACE. ANY
 MISSING DEVICES WILL HAVE TO BE ADDED FOR FINAL
 INSPECTION AND INCLUDED IN AN AS-BUILT DRAWING WHICH IS
 TO BE APPROVED BY THE CITY OF WEST PALM BEACH.
 A RE-ACCEPTANCE TEST REPORT AS REQUIRED BY NFPA 72
 SECTION 14.4.2 SHALL BE PROVIDED FOR FIRE & ELECTRICAL
 INSPECTORS AND INCLUDED IN THE SYSTEM LOG BOOK.
  
2015-05-08 15:07:05THE FIRE ALARM PLANS AS SUBMITTED DO NOT MEET THE
 REQUIREMENTS OF FBC 907.4.1 OR NFPA 10.15, 17.14.6. IF
 THESE AREAS ARE PROTECTED AS PART OF AN EXISTING
 SYSTEM, THAT SHALL BE SO NOTED ON THE PLANS AND LABELED
 AS EXISTING. FURTHERMORE, A NOTE AS TO THE MUTING OF
 ALL AUXILIARY AUDIO VIA THE FIRE ALARM AN EVENT OF AN
 ALARM CONDITION SHALL BE MADE.