Plan Review Notes For Permit 15040783 |
Permit Number |
15040783 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-20 09:20:26 | ELECTRICAL PROVISO: | | BECAUSE THIS IS AN ADDITION TO AN EXISTING SYSTEM, IT | | IS ASSUMED THAT ALL REQUIRED DEVICES SUBORDINATE TO | | THIS INSTALLATION AND THE SURROUNDING AREAS THOUGH NOT | | INDICATED ON THE DRAWINGS AS EXISTING ARE IN PLACE. ANY | | MISSING DEVICES WILL HAVE TO BE ADDED FOR FINAL | | INSPECTION AND INCLUDED IN AN AS-BUILT DRAWING WHICH IS | | TO BE APPROVED BY THE CITY OF WEST PALM BEACH. | | A RE-ACCEPTANCE TEST REPORT AS REQUIRED BY NFPA 72 | | SECTION 14.4.2 SHALL BE PROVIDED FOR FIRE & ELECTRICAL | | INSPECTORS AND INCLUDED IN THE SYSTEM LOG BOOK. | | | 2015-05-08 15:07:05 | THE FIRE ALARM PLANS AS SUBMITTED DO NOT MEET THE | | REQUIREMENTS OF FBC 907.4.1 OR NFPA 10.15, 17.14.6. IF | | THESE AREAS ARE PROTECTED AS PART OF AN EXISTING | | SYSTEM, THAT SHALL BE SO NOTED ON THE PLANS AND LABELED | | AS EXISTING. FURTHERMORE, A NOTE AS TO THE MUTING OF | | ALL AUXILIARY AUDIO VIA THE FIRE ALARM AN EVENT OF AN | | ALARM CONDITION SHALL BE MADE. |
|