2015-05-05 11:06:46***PROVISO***
 ***ISSUED AT CONTRACTOR'S RISK****
  
 FBC R310, FBC EB 604.1. FOR SLEEPING ROOM WINDOWS, THE
 CLEAR EMERGENCY ESCAPE AND RESCUE OPENING CANNOT BE
 REDUCED BY MORE THAN 5%.
  
 38" HIGH WINDOWS ARE SHOWN ON THE FLOOR PLAN. IF ANY OF
 THE 38" HIGH WINDOWS ARE LOCATED IN SLEEPING ROOMS,
 SUBMIT A REVISION WITH CALCULATIONS TO SHOW THAT THE
 CLEAR OPENING IS NOT REDUCED BY MORE THAN 5%.
  
  
  