Plan Review Notes
Plan Review Notes For Permit 15040735
Permit Number 15040735
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-23 08:59:50****CORRECTIONS****
 ****REVISED 5/6/15****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SCOPE NOT CLEAR. APPLICATION STATES "REPLACE TUB
 WALLS & TILE."
  
 REPLACING THE TUB AND WALLS AND TILE? REPACING TILE
 ONLY? REPLACING THE TUB WALLS AND THEN TILE OVER? A
 PLAN WAS PROVIDED BUT IS DIFFICULT TO UNDERSTAND.
  
 SEE FBC 107, PLANS TO SHOW NATURE AND SCOPE OF WORK.
 PROVIDE A BASIC PLAN WHICH SHOWS LOCATION OF PROPOSED
 IMPROVEMENT WITHIN THE UNIT. THE PLAN SHOULD INCLUDE A
 WRITTEN DESCRIPTION WHICH CLARIFIES SCOPE OF WORK.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 3. PROVIDE THE FOLLOWING TESTS FOR FLOOR TILE
 UNDERLAYMENT:
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  
  
  
  
  