Plan Review Notes For Permit 15040688 |
Permit Number |
15040688 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-21 16:36:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE SUBMITTAL AND INSTALLATION SHALL COMPLY WITH THE | | REQUIREMENTS OF NFPA 24 | | | | A SITE PLAN WAS NOT PROVIDED. A DETAILED SITE PLAN | | SHALL BE SUBMITTED. SHOWING ALL LINE SIZES AND | | LOCATIONS. | | | | THERE IS INSUFFICIENT DETAIL PROVIDED WITH THIS | | SUBMITTAL. THE INFORMATION REQUIREMENTS ARE OUTLINED IN | | NFPA 24, INCLUDING IN BUT NOT LIMITED TO, 4.1, PLANS. | | | | NO WORK IS TO BE STARTED WITHOUT A PERMIT BEING ISSUED. | | | | ALL UNDERGROUND WORK SHALL BE LEFT UNCOVERED UNTIL ALL | | CITY AND FIRE INSPECTIONS ARE COMPLETED. | | | | |
|