Plan Review Notes For Permit 15040646 |
Permit Number |
15040646 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-21 13:04:23 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | 1) ON SHEET T THERE ARE INCORRECT REFERENCES TO THE | | FIRE CODE: THE PROPOSED PROJECT SHALL MEET THE | | REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE | | PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1 | | AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR | | STANDARDS. | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 13, 2010 EDITION. | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 72, 2010 EDITION. | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 241, 2009 EDITION. | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 10, 2010 EDITION. | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | |
|