Plan Review Notes For Permit 15040628 |
Permit Number |
15040628 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-21 08:25:01 | 1) SUBMIT A ROOF PLAN SHOWING THE LOCATION AND SIZE OF | | THE GUTTERS AND DOWNSPOUTS. WPB AMEND. TO 2010 FBC SEC. | | 107,2,1, | | 2) THE GUTTERS SHALL BE SIZED PER TABLE 1106.6 OF THE | | 2010 FPC. SUBMIT CALCULATIONS, | | 3) SUBMIT A PLAN THAT SHOWS THE SQUARE FOOTAGE OF THE | | ROOF THAT IS DRAINED BY EACH GUTTER. WPB AMEND. TO 2010 | | FBC SEC.107.2.1. | | 4) THE DOWNSPOUTS SHALL BE SIZED PERR THE 2010 FBC | | TABLE 1106.2 (1) FOR CIRCULAR VERTICAL CONDUCTORS AND | | LEADERS AND TABLE 1106.2 (2) FOR RECTANGULAR VERTICAL | | CONDUCTORS AND LEADERS. | | 5) RAINWATER LEADERS SHALL DISCHARGE A MINIMUM OF ONE | | FOOT AWAY FROM THE STRUCTURE SIDEWALL PER THE 2010 FBC | | SEC.1503.7. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|