2015-04-21 08:25:011) SUBMIT A ROOF PLAN SHOWING THE LOCATION AND SIZE OF
 THE GUTTERS AND DOWNSPOUTS. WPB AMEND. TO 2010 FBC SEC.
 107,2,1,
 2) THE GUTTERS SHALL BE SIZED PER TABLE 1106.6 OF THE
 2010 FPC. SUBMIT CALCULATIONS,
 3) SUBMIT A PLAN THAT SHOWS THE SQUARE FOOTAGE OF THE
 ROOF THAT IS DRAINED BY EACH GUTTER. WPB AMEND. TO 2010
 FBC SEC.107.2.1.
 4) THE DOWNSPOUTS SHALL BE SIZED PERR THE 2010 FBC
 TABLE 1106.2 (1) FOR CIRCULAR VERTICAL CONDUCTORS AND
 LEADERS AND TABLE 1106.2 (2) FOR RECTANGULAR VERTICAL
 CONDUCTORS AND LEADERS.
 5) RAINWATER LEADERS SHALL DISCHARGE A MINIMUM OF ONE
 FOOT AWAY FROM THE STRUCTURE SIDEWALL PER THE 2010 FBC
 SEC.1503.7.
  