2015-05-28 09:05:00 | ****CORRECTIONS**** |
| ***COURTESY REVIEW VIA EMAIL*** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 |
| [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2010 |
| |
| TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED |
| |
| TEST REPORTS FOR US FLOORS LLC ENGINEERED VINYL PLANK |
| FLOORING OVER 6 INCH CONCRETE SLAB WITH INSULATED |
| DRYWALL CEILING |
| |
| 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| NOT BE ALTERED. |
| |
| THE TEST SENT VIA EMAIL INCLUDES A SUSPENDED DRYWALL |
| CEILING ASSEMBLY; PLEASE REQUEST A TEST WITHOUT THE |
| SUSPENDED CEILING FROM THE MANUFACTURER. |
| |
| 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| BELOW WILL NOT BE ALTERED. |
| |
| THE TEST SENT VIA EMAIL INCLUDES A SUSPENDED DRYWALL |
| CEILING ASSEMBLY; PLEASE REQUEST A TEST WITHOUT THE |
| SUSPENDED CEILING FROM THE MANUFACTURER. |
| |
| 3. OK (FLAME SPREAD TEST PROVIDED VIA EMAIL WAS |
| ACCEPTABLE). |
| |
| 4. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD, |
| PROFIT, EVEN IF PROVIDED BY OTHERS FBC 109. |
| |