2015-04-29 11:13:10REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE RISER DIGRAM INDICATES A 200AMP MAIN FEEDING A
 100AMP PANEL. PROVIDE A CIRCUIT DIRECTORY FOR THE
 METER/MAIN COMBO PANEL. INDICATE THE OCPD FEEDING THE
 EXISTING 100AMP PANEL. NEC 408.4,
 2) INDICATE TWO GROUNDING ELECTRODES. NEC 250.56
 3) PROVIDE THE FEEDER SIZE AND TYPE FEEDING THE
 EXISTING 100AMP PANEL. WPB AMENDMENTS TO FBC
 107.3.5.1.2
 4) PROVIDE THE REQUIRED INTERSYSTEM BONDING DEVICE.
 NEC250.94
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]