Plan Review Notes For Permit 15040559 |
Permit Number |
15040559 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-17 11:15:28 | 1) ROMEX APPROVED FOR INSTALLATION SLEVED IN PVC | | CONDUIT BUT AN APPROVED BUSHING IS REQUIRED WHER THE | | CABLE EXITS THE RACEWAY. NEC 334.15(C) | | | | 2) NMC ROMEX IS APPROVED FOR DAMP LOCATION. TYPE NM | | ROMEX IS ONLY APPROVED FOR DRY LOCATION. NEC | | 334.10(B)(1) | | | | 3) #2CU GROUNDING ELECTRODE CONDUCTOR REQUIRED DUE TO | | SIZE OF THE SERVICE ENTRANCE CONDUCTORS. NEC 250.66 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|