Plan Review Notes
Plan Review Notes For Permit 15040559
Permit Number 15040559
Review Stop E
Sequence Number 2
Notes
Date Text
2015-04-17 11:15:281) ROMEX APPROVED FOR INSTALLATION SLEVED IN PVC
 CONDUIT BUT AN APPROVED BUSHING IS REQUIRED WHER THE
 CABLE EXITS THE RACEWAY. NEC 334.15(C)
  
 2) NMC ROMEX IS APPROVED FOR DAMP LOCATION. TYPE NM
 ROMEX IS ONLY APPROVED FOR DRY LOCATION. NEC
 334.10(B)(1)
  
 3) #2CU GROUNDING ELECTRODE CONDUCTOR REQUIRED DUE TO
 SIZE OF THE SERVICE ENTRANCE CONDUCTORS. NEC 250.66
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]