Plan Review Notes For Permit 15040559 |
Permit Number |
15040559 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-16 14:09:09 | 1) THE TYPE AND SIZE OF ROMEX PROPOSED IS NOT CLEAR. | | PLEASE CLARIFY THE TYPE AND SIZE OF CABLE THAT IS | | PROPOSED FOR THE INSTALLATION OF THE FEEDER FROM THE | | SERVICE DISCONNECT TO THE PANEL. THE SIZE APPEARS TO BE | | INDICATED AS #6-3-2 + GRD. PLEASE BE MORE SPECIFIC AS | | TO HOW MANY CONDUCTOR CABLE THIS IS . | | | | 2) THE TYPE OF CONDUCTORS FOR THE 100AMP UNIT #1 ARE | | NOT SHOW. PLEASE IDENTIFY THE TYPE OF CONDUCTORS | | PROPOSED TO BE INSTALLED FROM THE SERVICE DISCONNECT TO | | THE PANEL IN UNIT #1 | | | | 3) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR IS | | INDICATED TO BE A #6 SOLID. THE GEC IS BASED ON THE | | SIZE AND TYPE OF THE SERVICE ENTRANCE CONDUCTORS | | HOWEVER THE SERVICE ENTRANCE CONDUCTORS SIZE AND TYPE | | IS NOT SHOWN ON THIS PLAN. PROVIDE THE SIZE AND TYPE OF | | THE SERVICE ENTRANCE CONDUCTORS AND GEC | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|