2015-04-15 13:13:22APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 THE PLAN IS CALLING FOR THE REMOVAL OF AN OUTLET IN ONE
 BATHROOM. SEE THE CODE ARTICLE BELOW THAT STATES A GFI
 OUTLETS IS REQUIRED WITHIN 3FT OF A RESIDENTIAL
 BATHROOM SINK.
 THEREFORE PROVIDE A GFI RECEPTACLE WITHIN 3FT OF EACH
 OF THE BATHROOM SINKS.
  
 1) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL
 OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE
 BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE
 COUNTERTOP. ACCORDING TO THE CONTRACTOR. THERE IS AN
 EXISTING OUTLET WITHIN THE 3' SPACE NEEDED TO COMPLY
 WITH THIS CODE. NEC 210.52(D)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  