Plan Review Notes
Plan Review Notes For Permit 15040521
Permit Number 15040521
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-16 07:04:441) THE INTERCEPTOR DETAIL DOES NOT SHOW THE INLET AND
 OUTLET PIPING DETAILS PER THE 2010 FPC SEC.1003.5.3.
 2) THE CONTRACTOR STATED TO ME THAT THE EXISTING TANKS
 ARE 2450 GALLONS BUT THESE TANKS ARE 3,000 GALLONS.
 CLARIFY. THE 2010 FL. PLUMBING CODE SEC.1003.5.1 STATES
 THE MAXIMUM VOLUME OF AN INDIVIDUAL GREASE INTERCEPTOR
 CHAMBER SHALL BE 1250 GALLONS.WHEN THE CAPACITY IS
 GREATER THAN 1250 GALLONS, THEY SHALL BE INSTALLED IN
 SERIES. SUBMIT DOCUMENTATION FROM THE HOSPITAL
 CONFIRMING THE CAPACITY OF THE EXISTING TANKS ( A
 RECENT PUMP-OUT BILL THAT SPECIFIES THE CAPACITY WILL
 SUFFICE).
 3) TWO DIFFERENT TANK SPECIFICATIONS HAVE BEEN
 SUBMITTED AND THEY REFERENCE TWO DIFFERENT STATE
 APPROVAL NUMBERS.CLARIFY. SUBMIT A COPY OF THE STATE
 APPROVAL OF THE TANK THAT WILL BE INSTALLED.WPB
 AMENDMENTS TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  