Plan Review Notes For Permit 15040521 |
Permit Number |
15040521 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-16 07:04:44 | 1) THE INTERCEPTOR DETAIL DOES NOT SHOW THE INLET AND | | OUTLET PIPING DETAILS PER THE 2010 FPC SEC.1003.5.3. | | 2) THE CONTRACTOR STATED TO ME THAT THE EXISTING TANKS | | ARE 2450 GALLONS BUT THESE TANKS ARE 3,000 GALLONS. | | CLARIFY. THE 2010 FL. PLUMBING CODE SEC.1003.5.1 STATES | | THE MAXIMUM VOLUME OF AN INDIVIDUAL GREASE INTERCEPTOR | | CHAMBER SHALL BE 1250 GALLONS.WHEN THE CAPACITY IS | | GREATER THAN 1250 GALLONS, THEY SHALL BE INSTALLED IN | | SERIES. SUBMIT DOCUMENTATION FROM THE HOSPITAL | | CONFIRMING THE CAPACITY OF THE EXISTING TANKS ( A | | RECENT PUMP-OUT BILL THAT SPECIFIES THE CAPACITY WILL | | SUFFICE). | | 3) TWO DIFFERENT TANK SPECIFICATIONS HAVE BEEN | | SUBMITTED AND THEY REFERENCE TWO DIFFERENT STATE | | APPROVAL NUMBERS.CLARIFY. SUBMIT A COPY OF THE STATE | | APPROVAL OF THE TANK THAT WILL BE INSTALLED.WPB | | AMENDMENTS TO 2010 FBC SEC. 107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|