Plan Review Notes
Plan Review Notes For Permit 15040488
Permit Number 15040488
Review Stop B
Sequence Number 3
Notes
Date Text
2015-07-24 09:19:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE APPLICATION STATES "SEE ATTACHED" FOR PARCEL ID.
 THE PAGES WITH THE UNIT OWNERS, ADDRESSES, AND PARCEL
 ID ARE IN THE OLD VOIDED PACKAGE.
  
 THIS HAS BEEN ADDRESSED FOR YOU FOR THIS PERMIT
 APPLICATION. FOR FUTURE RESUBMITTALS, PLEASE ATTACH THE
 LIST OF PARCELS ASSOCIATED WITH EACH APPLICATION TO THE
 PERMIT APPLICATION OR REVISE THE PERMIT APPLICATIONS TO
 INCLUDE ALL PARCELS TO BE COVERED UNDER THE PERMIT.
  
 2. PER THE ENGINEERING SUBMITTED, APPROXIMATELY 150
 SQUARE FEET OF ROOF AREA WILL BE REQUIRED TO BE REMOVED
 AND REPLACED. PROVIDE PRODUCT APPROVAL AND INDICATE THE
 ASSEMBLY PROPOSED. IF THE DESIGN PRESSURES DO NOT MEET
 THE MINIMUM DESIGN PRESSURES REQUIRED, AND IF THE
 PRODUCT APPROVAL REQUIRES ENGINEERING, ENGINEERING IS
 REQUIRED.
  
 3. PROVIDE A COPY OF THE CHANGE ORDER FOR THE
 ADDITIONAL WORK (VALUE ADJUSTMENT).
  
  