Date |
Text |
2015-04-28 16:12:29 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FROM PREVIOUS REVIEW: |
| |
| 1-5. OK |
| |
| 6. APPLICATION AND PROPOSAL SPECIFY GACO FLEX S2000, |
| 1.5 GALLONS PER 100 SF. SEE PAGE 3 OF THE NOA; TWO |
| COATS AT A MINIMUM RATE OF .75 GAL / 100' EACH ARE |
| REQUIRED. ALTHOUGH THE TOTAL GALLONS PER SF IS |
| CONSISTENT WITH THE NOA, THE APPLICATION METHOD |
| PROPOSED ("A TOP COAT") DOES NOT COMPLY WITH THE |
| REQUIREMENTS OF THE NOA. |
| |
| 3RD REVIEW - CONTRACTOR HAS PROVIDED SPEC SHEETS WHICH |
| ALLOW 1 COAT RATHER THAN 2. THE MIAMI DADE NOA SHOULD |
| NOT BE USED AS THIS IS NOT THE APPLICATION FOR THIS |
| JOB. HOWEVER, FBC 1507.15.1 REQUIRES THAT |
| LIQUID-APPLIED ROOF COATINGS COMPLY WITH ONE OF SEVERAL |
| STANDARDS. THE MIAMI DADE NOA INDICATES THAT THE S2000 |
| COMPLIES WITH ASTM D 6694. I WAS UNABLE TO LOCATE ANY |
| ONE OF THE REQUIRED ASTM STANDARD OPTIONS IN THE SPEC |
| SHEET. |
| |
| AS YOU DO NOT WISH TO INSTALL THIS PRODUCT AS REQUIRED |
| BY THE NOA, PLEASE REMOVE THE NOA. PROVIDE SOMETHING |
| WHICH PROVIDES DOCUMENTATION THAT THIS PRODUCT COMPLIES |
| WITH ONE OF THE OPTIONS LISTED IN FBC 1507.15.1. |
| |
| 7-8. OK |
| |
| 9. PERMIT 02090676 FOR 7404 74TH WAY IS EXPIRED (DID |
| NOT OBTAIN A FINAL INSPECTION). IF THIS PROJECT |
| INCLUDES THIS ADDRESS, THIS PERMIT IS TO BE RESOLVED |
| PRIOR TO ISSUANCE OF THE PERMIT FOR THAT BUILDING. |
| |
| 3RD REVIEW - AS THIS JOB WILL PROGRESS QUICKLY, |
| CONTRACTOR IS TO WRITE A LETTER STATING THAT THEY |
| UNDERSTAND THAT THIS BUILDING FOR PERMIT 02090676 WILL |
| NOT BE DONE AT THIS TIME AS A REISSUE PERMIT HAS NOT |
| BEEN APPLIED FOR. |
| |
| WHEN RESUBMITTING, PLEASE PROVIDE FIVE COMPLETE |
| COLLATED SETS OF DOCUMENTS FOR PERMIT ISSUANCE (REMOVE |
| MIAMIDADE NOA, INSERT DOCUMENT WHICH INCLUDES THE ASTM |
| STANDARD). |
| |
| |
| |
| |