Date |
Text |
2015-04-21 12:34:14 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FROM PREVIOUS LIST: |
| |
| 1. SEE PREVIOUS ITEM #1. PER CONVERSATION, CONTRACTOR |
| WILL USE A MASTER. A MINIMUM OF THREE FIELD SETS WAS |
| RECOMMENDED (SO FOUR SETS TOTAL WOULD NEED TO BE |
| SUBMITTED). ONLY ONE SET WAS SUBMITTED. SEE FBC 107, A |
| MINIMUM OF TWO COMPLETE COLLATED SETS OF DOCUMENTS |
| REQUIRED FOR PERMIT ISSUANCE. |
| |
| TO MAKE THIS VERY CLEAR - CONTRACTOR IS TO PROVIDE A |
| MINIMUM OF TWO COLLATED IDENTICAL SETS OF DOCUMENTS FOR |
| PERMIT ISSUANCE. IT IS NOT CLEAR WHY, WHEN SUBMITTAL OF |
| FIVE SETS WAS DISCUSSED, ONE WAS SUBMITTED. |
| |
| 2. PROVIDE INFORMATION REGARDING THE EXISTING ROOF. THE |
| PERMIT DOCUMENTS SHOULD INCLUDE ALL INFORMATION |
| REQUIRED TO DEMONSTRATE CODE COMPLIANCE, FBC 107. |
| |
| 2ND REVIEW, PERMIT DOCUMENTS SHOULD INCLUDE SOMETHING |
| WHICH STATE EXISTING ROOF TYPE. I HAVE HIGHLIGHTED |
| "TPO" ON ONE DOCUMENT. THIS COULD BE ONE POSSIBLE |
| METHOD OF INDICATING EXISTING ROOF TYPE, BUT THIS IS |
| THE CONTRACTOR'S RESPONSIBILITY. CONTRACTOR TO DO |
| ENOUGH RESEARCH TO DETERMINE EXISTING ROOF TYPE AND |
| SUITABILITY OF PROPOSED INSTALLATION, THEN PROVIDE |
| DOCUMENTS WHICH CLEARLY INDICATE EXISTING ROOF TYPE |
| DETERMINED BY CONTRACTOR. |
| |
| 3. 2ND REVIEW, A NEW NOA PROVIDED WITH "S-2000 |
| SOLVENTLESS SILICONE BASECOAST/TOPCOAT" HIGHLIGHTED. |
| |
| GACOWASH SPEC SHEET - OK |
| GACOFLEX E5320 SPEC SHEET - DOES NOT SPECIFICALLY STATE |
| THAT IT CAN BE USED WITH TPO ROOF - EITHER HIGHLIGHT |
| WHERE TPO IS SPECIFICALLY NAMED OR PROVIDE A LETTER |
| FROM THE MANUFACTURER SINCE TPO ROOF IS NOT INCLUDED IN |
| THE NOA |
| S20 SERIES SPEC SHEET - MENTIONS TPO BUT THE PRODUCT IN |
| THE NOA (S-2000 SOLVENTLESS SILICONE BASECOAST/TOPCOAT) |
| IS NOT NAMED. SOMETHING FROM THE MANUFACTURER SHOULD |
| TIE THIS SPEC SHEET TO THE PRODUCT PROPOSED. |
| |
| 4. OK |
| |
| 5. E5320 IS SPECIFIED AS A "PRIMER COAT" IN THE |
| PROPOSAL. PROVIDE MANUFACTURER SPEC SHEETS/INSTALLATION |
| INSTRUCTIONS, FBC 107. APPLICATION PROPOSES "PRIMER" AT |
| A RATE OF 1 GALLON / 250 SF. SINCE THIS PRODUCT DOES |
| NOT APPEAR TO HAVE A PRODUCT APPROVAL (IT IS ONLY |
| REFERENCED IN THE ROOF COATING SYSTEMS IN THE NOA), |
| PROVIDE MANUFACTURER SPEC SHEETS WHICH INCLUDE |
| INFORMATION ABOUT THE PRODUCT AND THE RECOMMENDED |
| APPLICATION METHOD AND RATE. ALTHOUGH IT DOES NOT HAVE |
| A PRODUCT APPROVAL, IT APPEARS THAT THIS IS THE PRODUCT |
| WHICH ASSURES THE BOND REQUIRED FOR WIND RESISTANCE FBC |
| 1609. |
| |
| 2ND REVIEW, THE RATE WHICH CONTRACTOR PROPOSES IS FOR A |
| CONCRETE DECK. PROVIDE SOMETHING FROM THE MANUFACTURER |
| TO INDICATE THAT 1 GALLON PER 250 SF IS ACCEPTABLE. |
| |
| 6. APPLICATION AND PROPOSAL SPECIFY GACO FLEX S2000, |
| 1.5 GALLONS PER 100 SF. SEE PAGE 3 OF THE NOA; TWO |
| COATS AT A MINIMUM RATE OF .75 GAL / 100' EACH ARE |
| REQUIRED. ALTHOUGH THE TOTAL GALLONS PER SF IS |
| CONSISTENT WITH THE NOA, THE APPLICATION METHOD |
| PROPOSED ("A TOP COAT") DOES NOT COMPLY WITH THE |
| REQUIREMENTS OF THE NOA. |
| |
| NOT ADDRESSED. |
| |
| 7. OK |
| |
| 8. AS ITEMS 5 AND 6 WERE NOT ADDRESSED, COMMENT STILL |
| APPLIES - IF METHOD OF INSTALLATION AS PROPOSED ON THE |
| APPLICATION IS NOT APPROVED, NEW APPLICATIONS WILL BE |
| REQUIRED. |
| |
| 9. PERMIT 02090676 FOR 7404 74TH WAY IS EXPIRED (DID |
| NOT OBTAIN A FINAL INSPECTION). IF THIS PROJECT |
| INCLUDES THIS ADDRESS, THIS PERMIT IS TO BE RESOLVED |
| PRIOR TO ISSUANCE OF THE PERMIT FOR THAT BUILDING. |
| |