2015-06-24 17:20:20RECOVERY ROOF FOURTH BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- NEW FLORIDA PRODUCT APPROVAL FL5680-R14 SUBMITTED:
 SELECTED RECOVERY ASSEMBLY R-28 CAN NOT BE USED BECAUSE
 THIS ASSEMBLY MAXIMUM DESIGN PRESSURE IS - 75 PSF. THIS
 DESIGN PRESSURE DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON THE ECS REPORT SUBMITTED.
 NOTE #9 ON PAGE 2 OF 76 STATES "FOR FULLY BONDED
 ASSEMBLIES, THE MAXIMUM DESIGN PRESSURE FOR THE
 SELECTED ASSEMBLY SHALL MEET OR EXCEED CRITICAL DESIGN
 PRESSURE DETERMINED IN ACCORDANCE WITH FBC CHAPTER 16,
 AND NO RATIONAL ANALYSIS IS PERMITTED."
  
 NOTE: PER CONVERSATION WITH ROBERT BROWN (BUILDING
 OFFICIAL) THERE ARE TWO OPTIONS SINCE THE PROPOSED
 RECOVERY ASSEMBLY IS A FULLY BONDED ASSEMBLY:
  
 A) PROVIDE AN APPROVED ASSEMBLY THAT MEETS THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. OR
  
 B) HIRE AN STATE CERTIFIED ROOFING CONSULTANT TO
 PROVIDE COMPLETE ANALYSIS OF PROPOSED ROOFING ASSEMBLY.
 FOR THIS OPTION, PLEASE CONTACT ROBERT BROWN
 (561)805-6652 FOR PROPER DOCUMENTATION.
  
  
 NOTE:
 MOISTURE TEST SUBMITTED DOESN'T MEET THE STANDARD
 PROCEDURES FOR ROOF MOISTURE SURVEYS (TAS 126-95).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]