2015-06-12 16:41:28 | RECOVERY ROOF THIRD BUILDING REVIEW CHECKLIST. |
| CODE: 2010 FBC. |
| |
| NOTE: BASED ON THE ROOFING PRODUCT APPROVAL SUBMITTED |
| THE INFORMATION BELOW IS REQUIRED. THAT'S WHY THE |
| PRODUCT APPROVAL WAS REQUESTED SINCE THE FIRST REVIEW, |
| BUT IT WAS NEVER SUBMITTED UNTIL NOW. |
| |
| 1- FLORIDA PRODUCT APPROVAL SUBMITTED: |
| A) FLORIDA PRODUCT APPROVAL FL16730-R3 SUBMITTED WAS |
| REVISED BY FLORIDA PRODUCT APPROVAL FL 16730-R4. |
| PROVIDE COPY OF CURRENT FLORIDA PRODUCT APPROVAL |
| FL16730-R4. FL16730-R3 IS NO LONGER VALID. |
| |
| B) SELECTED ASSEMBLY R-20 CAN NOT BE USED BECAUSE THIS |
| ASSEMBLY MAXIMUM DESIGN PRESSURE IS -45PSF. THIS DESIGN |
| PRESSURE DOESN'T MEET THE DESIGN PRESSURES CALCULATED |
| BY THE ENGINEER ON THE ECS REPORT SUBMITTED. IN |
| ADDITION, THIS ASSEMBLY HAS AN ASTERISK AFTER THE |
| DESIGN PRESSURE OF -45PSF. NOTE #10 OF THE FLORIDA |
| PRODUCT APPROVAL FL16730-R4 (AND FL16730-R3) STATES |
| THAT "FOR ASSEMBLIES MARKED WITH AN ASTERISK*, THE |
| MAXIMUM DESIGN PRESSURE (MDP) LIMITATION LISTED SHALL |
| BE APPLICABLE TO ALL ROOF PRESSURE ZONES (I.E., FIELD, |
| PERIMETERS AND CORNERS). NEITHER RATIONAL ANALYSIS, NOR |
| EXTRAPOLATION IS PERMITTED FOR ENHANCED ATTACHMENT AT |
| ENHANCED PRESSURE ZONES (I.E., PERIMETERS, CORNERS AND |
| EXTENDED CORNERS)." |
| |
| NOTES: |
| (1) NEED TO SELECT AN ASSEMBLY THAT MEETS THE |
| CALCULATED DESIGN PRESSURES OR THAT ALLOWS RAS 117 |
| CALCULATIONS (NAIL ENHANCING CALCULATIONS TO INCREASE |
| THE DESIGN PRESSURES). |
| |
| (2) IF RAS 117 CALCULATIONS ARE REQUIRED, THEN THEY |
| NEED TO BE SIGNED AND SEALED. |
| |
| C) LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL |
| FL16730-R4 STATES THAT " FOR RECOVER INSTALLATIONS, THE |
| EXISTING ROOF SHALL BE EXAMINED IN ACCORDANCE WITH FBC |
| 1521.". SECTION 1521.12 REQUIRES A MOISTURE CONTENT |
| TEST (TAS 126). NEED TO PROVIDE COPY OF THIS TEST. |
| |