Plan Review Notes
Plan Review Notes For Permit 15040458
Permit Number 15040458
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-16 16:50:47RECOVERY ROOF THIRD BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLORIDA PRODUCT APPROVAL SUBMITTED:
 A) FLORIDA PRODUCT APPROVAL FL16730-R3 SUBMITTED WAS
 REVISED BY FLORIDA PRODUCT APPROVAL FL 16730-R4.
 PROVIDE COPY OF CURRENT FLORIDA PRODUCT APPROVAL
 FL16730-R4. FL16730-R3 IS NO LONGER VALID.
  
 B) SELECTED ASSEMBLY R-20 CAN NOT BE USED BECAUSE THIS
 ASSEMBLY MAXIMUM DESIGN PRESSURE IS -45PSF. THIS DESIGN
 PRESSURE DOESN'T MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER ON THE ECS REPORT SUBMITTED. IN
 ADDITION, THIS ASSEMBLY HAS AN ASTERISK AFTER THE
 DESIGN PRESSURE OF -45PSF. NOTE #10 OF THE FLORIDA
 PRODUCT APPROVAL FL16730-R4 (AND FL16730-R3) STATES
 THAT "FOR ASSEMBLIES MARKED WITH AN ASTERISK*, THE
 MAXIMUM DESIGN PRESSURE (MDP) LIMITATION LISTED SHALL
 BE APPLICABLE TO ALL ROOF PRESSURE ZONES (I.E., FIELD,
 PERIMETERS AND CORNERS). NEITHER RATIONAL ANALYSIS, NOR
 EXTRAPOLATION IS PERMITTED FOR ENHANCED ATTACHMENT AT
 ENHANCED PRESSURE ZONES (I.E., PERIMETERS, CORNERS AND
 EXTENDED CORNERS)."
  
 NOTES:
 (1) NEED TO SELECT AN ASSEMBLY THAT MEETS THE
 CALCULATED DESIGN PRESSURES OR THAT ALLOWS RAS 117
 CALCULATIONS (NAIL ENHANCING CALCULATIONS TO INCREASE
 THE DESIGN PRESSURES).
  
 (2) IF RAS 117 CALCULATIONS ARE REQUIRED, THEN THEY
 NEED TO BE SIGNED AND SEALED.
  
  