Plan Review Notes
Plan Review Notes For Permit 15040433
Permit Number 15040433
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-15 10:05:201) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 PLUMBING WORK TO BE DONE. SHOW ORIGINATION AND
 TERMINATION POINTS OF ALL PIPING AND PIPE SIZES. WPB
 AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 2) THE DOCUMENT SUBMITTED FROM LIBERTY PUMPS IS LACKING
 INFORMATION REQUIRED BY THE PLUMBING CODE. REFER TO THE
 2010 FL. PLUMBING CODE SECS.712.3.2 FOR THE MINIMUM
 SIZE OF THE SUMP PIT.
 3) THE SUMP PIT SHALL BE VENTED PER FPC SEC.712.3.2 AND
 CHAPTER 9.
 4) THE EJECTOR PIPING SHALL CONNECT TO THE DRAINAGE
 SYSYTEM IN ACCORDANCE WITH THE 2010 FPC SEC. 712.3.5.
 5) THE MINIMUM CAPACITY OF THE PUMP SHALL COMPLY WITH
 TABLE 712.4.2.
 6) SUBMIT MANUF. SPECIFICXATIONS FOR THE PUMP.
 7) DRINKING FOUNTAINS SHALL COMPLY WITH FL.
 ACCESSIBILITY CODE SECS. 305 & 602.2 FOR CLEAR FLOOR
 SPACE REQS.
 8) THE PLACEMENT OF THE DRINKING FOUNTAIN SHALL NOT
 INTERFERE WITH THE APPROACH TO THE DOOR FROM THE
 EXTERIOR FOR HANDICAP ACCESSIBILTY MANEUVERING
 CLEARANCES.. A MINIMUM OF 18 INCHES CLEARANCE SHALL BE
 PROVIDED ADJACENT TO THE LATCH SIDE OF THE DOOR.
  