Plan Review Notes For Permit 15040433 |
Permit Number |
15040433 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-15 10:05:20 | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | PLUMBING WORK TO BE DONE. SHOW ORIGINATION AND | | TERMINATION POINTS OF ALL PIPING AND PIPE SIZES. WPB | | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. | | 2) THE DOCUMENT SUBMITTED FROM LIBERTY PUMPS IS LACKING | | INFORMATION REQUIRED BY THE PLUMBING CODE. REFER TO THE | | 2010 FL. PLUMBING CODE SECS.712.3.2 FOR THE MINIMUM | | SIZE OF THE SUMP PIT. | | 3) THE SUMP PIT SHALL BE VENTED PER FPC SEC.712.3.2 AND | | CHAPTER 9. | | 4) THE EJECTOR PIPING SHALL CONNECT TO THE DRAINAGE | | SYSYTEM IN ACCORDANCE WITH THE 2010 FPC SEC. 712.3.5. | | 5) THE MINIMUM CAPACITY OF THE PUMP SHALL COMPLY WITH | | TABLE 712.4.2. | | 6) SUBMIT MANUF. SPECIFICXATIONS FOR THE PUMP. | | 7) DRINKING FOUNTAINS SHALL COMPLY WITH FL. | | ACCESSIBILITY CODE SECS. 305 & 602.2 FOR CLEAR FLOOR | | SPACE REQS. | | 8) THE PLACEMENT OF THE DRINKING FOUNTAIN SHALL NOT | | INTERFERE WITH THE APPROACH TO THE DOOR FROM THE | | EXTERIOR FOR HANDICAP ACCESSIBILTY MANEUVERING | | CLEARANCES.. A MINIMUM OF 18 INCHES CLEARANCE SHALL BE | | PROVIDED ADJACENT TO THE LATCH SIDE OF THE DOOR. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|