Plan Review Notes For Permit 15040430 |
Permit Number |
15040430 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-27 16:03:17 | 1ST REVIEW: FBC 2010 | | | | FBC- 107.3.5.3 ? PROVIDE COMPLETE LOAD CALCULATIONS, | | PANEL SCHEDULES AND SHOW CIRCUITS ON FLOOR PLAN. SHOW | | EMERGENCY LIGHTING CIRCUITS PER NEC 700.12 (F) (4)- | | EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF | | SAME LOCAL AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY | | THE AREA, EM LIGHTS MAY BE ON OWN CIRCUIT. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|