2015-04-27 15:02:26PERMIT #15040415
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED:
 1) ADDRESS ALL PLAN REVIEWER COMMENTS. (BUILDING AND
 FIRE)
  
 2) PER NFPA 13, CHAPTER 8:
 8.15.7.1: UNLESS THE REQUIREMENTS OF 8.15.7.2,
 8.15.7.3, OR 8.15.7.4 ARE MET. SPRINKLERS SHALL BE
 INSTALLED UNDER EXTERIOR ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS EXCEEDING 4 FEET IN WIDTH.
  
 3) REVISE DRAWINGS TO SHOW THE INSTALLITION OF
 SPRINKLER COVERAGE UNDER THE CANOPIES OR PROVIDE PROOF
 OF COMPLIANCE WITH THE APPROPRIATE PROVISION ABOVE THAT
 WILL ALLOW FOR OMMISSION OF SPRINKLER COVERAGE.
  
  