Plan Review Notes
Plan Review Notes For Permit 15040413
Permit Number 15040413
Review Stop P
Sequence Number 1
Notes
Date Text
2015-05-10 08:09:021) SHT. P2.0 - THE MAXIMUM SQUARE FOOTAGE PERMITTED ON
 AN 8 INCH HORIZONTAL STORM DRAIN IS 9,200 SQ. FT. BASED
 ON 5 INCH RAINFALL PER TABLE 1106.3 OF 2010
 FBC-PLUMBING. THE PLAN IS SHOWING 12,200 SQ. FT. INTO
 EACH DRAIN. IS THIS NUMBER A TYPOGRAPHICAL ERROR? THE
 EXISTING PLANS SHOW A LOT LESS SQUARE FOOTAGE DRAINING
 INTO THESE DRAINS.
 2) SHT.A1.7 SHOW THESE DRAINA AS EXISTING BUT THE
 EXISTING PLANS AND THIS PLAN APPEARS TO SHOW THEM AS
 NEW. CLARIFY.
 3) AIR CONDITIONING DRAINS THAT DISCHARGE INTO ROOF
 DRAINS SHALL BE ADDED AS EACH GPM = 96 SQUARE FEET PER
 AIR CONDITIONING DRAIN PER 2010 FBC-PLUMBING
 SEC.1109.1. THIS SHALL BE SHOWN ON THE CALCULATIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR