Plan Review Notes For Permit 15040413 |
Permit Number |
15040413 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-10 08:09:02 | 1) SHT. P2.0 - THE MAXIMUM SQUARE FOOTAGE PERMITTED ON | | AN 8 INCH HORIZONTAL STORM DRAIN IS 9,200 SQ. FT. BASED | | ON 5 INCH RAINFALL PER TABLE 1106.3 OF 2010 | | FBC-PLUMBING. THE PLAN IS SHOWING 12,200 SQ. FT. INTO | | EACH DRAIN. IS THIS NUMBER A TYPOGRAPHICAL ERROR? THE | | EXISTING PLANS SHOW A LOT LESS SQUARE FOOTAGE DRAINING | | INTO THESE DRAINS. | | 2) SHT.A1.7 SHOW THESE DRAINA AS EXISTING BUT THE | | EXISTING PLANS AND THIS PLAN APPEARS TO SHOW THEM AS | | NEW. CLARIFY. | | 3) AIR CONDITIONING DRAINS THAT DISCHARGE INTO ROOF | | DRAINS SHALL BE ADDED AS EACH GPM = 96 SQUARE FEET PER | | AIR CONDITIONING DRAIN PER 2010 FBC-PLUMBING | | SEC.1109.1. THIS SHALL BE SHOWN ON THE CALCULATIONS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|