2015-06-04 08:45:53 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED |
| IMPROVEMENT IN RELATION TO THE EXISTING STRUCTURE AND |
| LOT LINES, FBC 107. THIS MAY BE DRAWN ONTO A COPY OF A |
| SURVEY, WITH DIMENSIONS. |
| |
| 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| THE SKYLIGHT AND ROOF COVERING ("MEMBRANE ROLL |
| ROOFING"), FAC9N-3, FBC 2010 RESIDENTIAL 301 (WIND |
| RESISTANCE). IF A FLORIDA STATE PRODUCT APPROVAL IS |
| PROVIDED, INCLUDE THE COVER SHEET, INSTALLATION |
| INSTRUCTIONS AND EVALUATION REPORT: |
| WWW.FLORIDABUILDING.ORG. |
| |
| IF A MIAMI DADE NOA IS USED, THE FLORIDA STATE PRODUCT |
| APPROVAL COVER SHEET IS NOT REQUIRED. |
| |
| 3. ON THE ROOF PRODUCT APPROVAL, INDICATE WHICH |
| ASSEMBLY IS PROPOSED. IF THE ASSEMBLY DOES NOT COMPLY |
| WITH THE DESIGN PRESSURE REQUIREMENTS FOR ZONES 2 AND |
| 3, INCLUDE ENHANCED FASTENING AS REQUIRED BY THE |
| PRODUCT APPROVAL. IF THE PRODUCT APPROVAL REQUIRES THAT |
| ENHANCED FASTENING BE CALCULATED BY A DESIGN |
| PROFESSIONAL, ENGINEERING REQUIRED. |
| |
| 4. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC |
| 2010 RESIDENTIAL 301 (WIND RESISTANCE - WIND SPEED, |
| EXPOSURE CLASSIFICATION). |
| |
| 5. IF RESUBMITTED PLANS ARE NOT CERTIFIED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), REVISE PLAN TO |
| INCLUDE WHICH OPTION OF METHOD FOR DESIGN WAS USED, FBC |
| 2010 RESIDENTIAL 301.2.1.1. CALCULATIONS MAY BE |
| REQUIRED. |
| |
| 6. PROVIDE A WALL SECTION DETAIL, FOUNDATION THROUGH |
| THE ROOF, FBC 107, FBC 2010 RESIDENTIAL 301. NO |
| INFORMATION WAS PROVIDED FOR THE CONCRETE SLAB, |
| FOOTINGS. |
| |
| 7. APPLICATION IS FOR A SCREEN PORCH, BUT SCREEN WAS |
| NOT SPECIFIED AND ATTACHMENT DETAILS NOT PROVIDED, FBC |
| 2010 RESIDENTIAL 301, FBC 107. REVISE PLAN TO INCLUDE |
| SCREEN DETAILS. |
| |
| 8. A DOOR IS SHOWN GRAPHICALLY BUT NOT SPECIFIED, FBC |
| 107. |
| |
| 9. PROVIDE A DETAIL FOR THE BALCONY EXTENSION (PLAN |
| STATES TO "NOTCH 2X8 INTO EXISTING 2X10 . . . "), FBC |
| 107. |
| |
| 10. 5/8" "ZIP ROOF SHEATHING" IS SPECIFIED, PROVIDE |
| FLORIDA STATE OR LOCAL PRODUCT APPROVAL (OR MIAMI DADE |
| NOA). |
| |
| 11. PROVIDE A STRUCTURAL DETAIL FOR THE KNEE WALL, FBC |
| 107. A DETAIL WAS PROVIDED BUT WATER BARRIER (MUST BE |
| DOUBLE FBC 2010 RESIDENTIAL 703.6.3 BOND BREAK), LATHE, |
| STUCCO, ETC. NOT SPECIFIED. |
| |
| 12. PLAN TO INCLUDE THE PRINTED NAME AND SIGNATURE OF |
| THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN, |
| FBC 107. |
| |
| |
| |
| |
| |
| |