2015-06-04 08:45:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED
 IMPROVEMENT IN RELATION TO THE EXISTING STRUCTURE AND
 LOT LINES, FBC 107. THIS MAY BE DRAWN ONTO A COPY OF A
 SURVEY, WITH DIMENSIONS.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE SKYLIGHT AND ROOF COVERING ("MEMBRANE ROLL
 ROOFING"), FAC9N-3, FBC 2010 RESIDENTIAL 301 (WIND
 RESISTANCE). IF A FLORIDA STATE PRODUCT APPROVAL IS
 PROVIDED, INCLUDE THE COVER SHEET, INSTALLATION
 INSTRUCTIONS AND EVALUATION REPORT:
 WWW.FLORIDABUILDING.ORG.
  
 IF A MIAMI DADE NOA IS USED, THE FLORIDA STATE PRODUCT
 APPROVAL COVER SHEET IS NOT REQUIRED.
  
 3. ON THE ROOF PRODUCT APPROVAL, INDICATE WHICH
 ASSEMBLY IS PROPOSED. IF THE ASSEMBLY DOES NOT COMPLY
 WITH THE DESIGN PRESSURE REQUIREMENTS FOR ZONES 2 AND
 3, INCLUDE ENHANCED FASTENING AS REQUIRED BY THE
 PRODUCT APPROVAL. IF THE PRODUCT APPROVAL REQUIRES THAT
 ENHANCED FASTENING BE CALCULATED BY A DESIGN
 PROFESSIONAL, ENGINEERING REQUIRED.
  
 4. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC
 2010 RESIDENTIAL 301 (WIND RESISTANCE - WIND SPEED,
 EXPOSURE CLASSIFICATION).
  
 5. IF RESUBMITTED PLANS ARE NOT CERTIFIED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), REVISE PLAN TO
 INCLUDE WHICH OPTION OF METHOD FOR DESIGN WAS USED, FBC
 2010 RESIDENTIAL 301.2.1.1. CALCULATIONS MAY BE
 REQUIRED.
  
 6. PROVIDE A WALL SECTION DETAIL, FOUNDATION THROUGH
 THE ROOF, FBC 107, FBC 2010 RESIDENTIAL 301. NO
 INFORMATION WAS PROVIDED FOR THE CONCRETE SLAB,
 FOOTINGS.
  
 7. APPLICATION IS FOR A SCREEN PORCH, BUT SCREEN WAS
 NOT SPECIFIED AND ATTACHMENT DETAILS NOT PROVIDED, FBC
 2010 RESIDENTIAL 301, FBC 107. REVISE PLAN TO INCLUDE
 SCREEN DETAILS.
  
 8. A DOOR IS SHOWN GRAPHICALLY BUT NOT SPECIFIED, FBC
 107.
  
 9. PROVIDE A DETAIL FOR THE BALCONY EXTENSION (PLAN
 STATES TO "NOTCH 2X8 INTO EXISTING 2X10 . . . "), FBC
 107.
  
 10. 5/8" "ZIP ROOF SHEATHING" IS SPECIFIED, PROVIDE
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL (OR MIAMI DADE
 NOA).
  
 11. PROVIDE A STRUCTURAL DETAIL FOR THE KNEE WALL, FBC
 107. A DETAIL WAS PROVIDED BUT WATER BARRIER (MUST BE
 DOUBLE FBC 2010 RESIDENTIAL 703.6.3 BOND BREAK), LATHE,
 STUCCO, ETC. NOT SPECIFIED.
  
 12. PLAN TO INCLUDE THE PRINTED NAME AND SIGNATURE OF
 THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN,
 FBC 107.
  
  
  
  
  
  