Plan Review Notes
Plan Review Notes For Permit 15040379
Permit Number 15040379
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-27 17:40:486/27/2015
 PROJECT: 1300 MANGONIA DR.
 PERMIT#: 15040379
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A RISER DIAGRAM AND A SITE PLAN INDICATING
 THE LOCATION OF THE MAIN DISCONNECT IN COMPLIANCE WITH
 NEC 230.70
 THE INTENT OF THE CODE IS TO HAVE THE MAIN DISCONNECT
 AS CLOSE AS PRACTICABLE TO THE SERVICE ENTRANCE. THE
 RISER INDICATES A METER BY ITSELF AND A MAIN BREAKER
 PANEL IN CLOSE PROXIMITY. THE FLOOR PLAN INDICATES THE
 PANEL ON THE INSIDE OF THE HOUSE IN A HALLWAY. THE
 RISER NEEDS TO INDICATE COMPLIANCE WITH THE NEC 230.70.
 EITHER THE MAIN IS IMMEDIATELY NEXT TO THE METER OR THE
 MAIN BREAKER PANEL IS INSTALLED IN CLOSE ENOUGH
 PROXIMITY TO COMPLY WITH NEC 230.70.
  
 2) PROVIDE A LOAD CALCULATION INDICATING THE 150AMP
 PANEL IS ADEQUATE FOR THE LOAD TO BE SERVED. NEC
 408.30, NEC 220.
 THE HEATING VS COOLING LOAD IS NOT REPRESENTED
 ACCURATELY. REVISE ACCORDINGLY.
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 4) AT LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE PROVIDED AT OR
 NEAR THE EQUIPMENT REQUIRING SERVICING. NEC 210.70(3)
  
 5) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 6) PROVIDE A DISCONNECT FOR A/C AHU IN ATTIC SPACE
 ABOVE PANEL. NEC 440.14
  
 7) INDICATE THE LOCATION OF ALL REQUIRED SMOKE
 DETECTORS. FBC-RESIDENTIAL 314 AND 315
 PROVIDE THE NAMES OF ALL ROOMS ON THE FLOOR PLAN.
  
 8) INDICATE GFI PROTECTION ON RECEPTACLES WHERE
 REQUIRED. NEC 210.8
  
 9) INDICATE GFI PROTECTION WITHIN SIGHT OF MECHANICAL
 EQUIPMENT. NEC 210.63
 OUTLETS STILL MISSING.
  
 10) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 11) 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN ADDITION
 TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER
 PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
  
 12) 210.52 (D) BATHROOMS.
 IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL
 BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE
 EDGE OF EACH BASIN.
 THERE IS A BATHROOM SHOWN ON THE FLOOR PLAN WITH TWO
 BASINS. EACH BASIN REQUIRES A GFI RECEPTACLE TO BE
 INSTALLED WITHIN 3FT.
  
 13) DISCONNECT REQUIRED FOR WATER HEATER. NEC 422.31
  
 14) INDICATE WHAT IS EXISTING TO REMAIN AND WHAT IS
 PROPOSED TO BE INSTALLED AS NEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,