2015-05-04 08:31:15 | 5/4/2015 |
| PROJECT: 1300 MANGONIA DR. |
| PERMIT#: 15040379 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) PROVIDE A RISER DIAGRAM AND A SITE PLAN INDICATING |
| THE LOCATION OF THE MAIN DISCONNECT IN COMPLIANCE WITH |
| NEC 230.70 |
| |
| 2) PROVIDE A LOAD CALCULATION INDICATING THE 150AMP |
| PANEL IS ADAQUATE FOIR THE LOAD TO BE SEARVED. NEC |
| 408.30, NEC 220. |
| |
| 3) PROVIDE A COMPLETE PANEL SCHEDULE WITH CIRCUIT |
| NUMBERS. NEC 408.4 |
| |
| 4) PROVIDE A FLOOR PLAN INDICATING THE COMPLETE SCOPE |
| OF WORK WITH CIRCUIT NUMBERS CORESPONDING TO THE PANEL |
| SCHEDULE. |
| |
| 5) PROVIDE DIMENSIONS FOR THE HALLWAY WHERE THE PANEL |
| IS LOCATED TO INDICATE COMPLIANCE WITH NEC 110.26 |
| |
| 6) PROVIDE A DISCONNECT FOR A/C AHU IN ATTIC SPACE |
| ABOVE PANEL. NEC 440.14 |
| |
| 7) INDICATE THE LOCATION OF ALL REQUIRED SMOKE |
| DETECTORS. FBC-RESIDENTIAL 314 AND 315 |
| |
| 8) INDICATE GFI PROTECTION ON RECEPTACLES WHERE |
| REQUIRED. NEC 210.8 |
| |
| 9) INDICATE GFI PROTECTION WITHIN SIGHT OF MECHANICAL |
| EQUIPMENT. NEC 210.63 |
| |
| 10) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
| |
| |