2015-04-24 11:49:38 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED |
| PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). |
| |
| THE FOLLOWING IS A CHECKLIST USED FOR FIELD INSPECTION. |
| |
| PLEASE PROVIDE ADDITIONAL INFORMATION WITH REGARDS TO |
| THE FOLLOWING PAY PARTICULAR ATTENTION TO THE REQUIRED |
| SIGNAGE. INDICATE THE REQUIRED SIGNAGE IN THE LOCATIONS |
| INDICATED BELOW: |
| |
| _____ PROVE # OF PV MODULES AND MODEL # MATCH SPEC |
| SHEETS [690.51] |
| _____ PV MODULES ARE LISTED TO UL 1703 STANDARD [110.3] |
| _____ ARRAY CONDUCTORS ARE NEATLY AND PROFESSIONALLY |
| HELD IN PLACE, GROUPED AND SEPARATED [690.4 B] |
| _____ CHECK CONNECTORS ARE POLARIZED, |
| NON-INTERCHANGEABLE AND UNIQUE [690.33 A] |
| _____ PROVE CONNECTORS STATE ?DO NOT DISCONNECT UNDER |
| LOAD? [690.33 E 2] |
| _____ CHECK THAT ELECTRICAL JUNCTION BOXES ARE READILY |
| ACCESSIBLE, LISTED AND SUITABLE FOR ENVIRONMENT (NEMA) |
| _____ ARRAY ATTACHMENTS ARE FASTENED AND SEALED |
| ACCORDING TO ATTACHMENT DETAIL IN PLANS |
| |
| CONDUCTORS |
| |
| _____ CONDUCTOR TYPES USE-2 OR PV WIRE FOR EXPOSED ARE |
| 90? C WET RATED AND SUNLIGHT RESISTANT [690.31(B)] |
| [NOTE 2008 AND 2011 NEC RESTRICT EXPOSED SINGLE |
| CONDUCTOR WIRING TO USE-2 AND LISTED PV WIRE]. IF IN |
| CONDUIT: RHW-2, THWN-2 OR XHHW-2 90? C WET RATED |
| CONDUCTORS ARE REQUIRED [310.15] |
| _____ CHECK CONDUCTORS INSULATION RATINGS AT 90? C [UL |
| 1703] TO ALLOW OPERATION AT ARE 70? C+ NEAR MODULES AND |
| IN CONDUIT EXPOSED TO SUNLIGHT (ADD 17-20? C TO AMBIENT |
| TEMPERATURE-2005NEC), (SEE TABLE 310.15(B)(2) IN |
| 2008NEC OR TABLE 310.15(B)(3)(C) IN 2011NEC) |
| |
| NOTE: TEMPERATURE-DERATED AMPACITY CALCULATIONS ARE |
| BASED ON 156% OF THE SHORT CIRCUIT |
| CURRENT (ISC) AND THE DERATED AMPACITY OF THE |
| OVERCURRENT DEVICE IS MATCHED [690.8,9] |
| |
| _____ STRAIN RELIEFS/CABLE CLAMPS ARE USED ON ALL CABLE |
| AND CORDS [300.4, 400.10] |
| _____ CONDUCTORS SHALL BE LISTED FOR THE APPLICATION |
| AND ENVIRONMENT. USE OF FINE STRANDED, FLEXIBLE |
| CONDUCTOR CABLES SHALL BE PROPERLY TERMINATED WITH |
| TERMINALS RATED FOR THESE CONDUCTORS [690.31 (E)(4)] |
| |
| |
| _____ EXPOSED CONDUCTORS SHALL BE READILY ACCESSIBLE |
| AND IN A RACEWAY IF OVER 30 VOLTS ? RACEWAYS CANNOT BE |
| INSTALLED ON MODULES. CONDUCTORS SHOULD BE INSTALLED |
| NOT READILY ACCESSIBLE. |
| _____ DC CONDUCTOR COLORS ARE THE SAME AS AC. GROUNDED |
| CONDUCTORS SHALL BE WHITE AND EQUIPMENT GROUNDING |
| CONDUCTORS ARE GREEN, GREEN/YELLOW OR BARE. |
| |
| NOTE: 1) |
| UNGROUNDED PV ARRAY CONDUCTORS ON UNGROUNDED ARRAYS |
| WILL NOT BE WHITE IN COLOR. |
| NOTE 2) TRADITIONALLY ALL PV SOURCE ARRAY WIRING WILL |
| BE BLACK. NON-BLACK COLORS HAVE PROVEN TO NOT BE AS |
| DURABLE IN THE UV RICH ENVIRONMENT AS BLACK. |
| |
| GROUNDING: |
| |
| _____ CHECK MODULE CONNECTIONS AND ALLOW FOR REMOVAL |
| WITHOUT INTERRUPT GROUNDED CONDUCTOR [690.4 C] |
| _____ 2 WIRE OVER 50 VOLTS SHALL BE GROUNDED [690.41] |
| _____ CHECK POINT OF SYSTEM GROUNDING CONNECTION |
| [690.42] IS AT ANY POINT ALONG PV OUTPUT CIRCUIT |
| _____ CHECK EQUIPMENT GROUNDING OF METAL PARTS ON SOLAR |
| PANEL FRAMES ARE GROUNDED PER 250.134 AND 250.136 |
| _____ INSURE EITHER UNIVERSAL GROUNDING CLIPS (UGC) OR |
| WEEBS? ARE LISTED AND IDENTIFIED FOR BONDING PANELS TO |
| GROUNDED MOUNTING STRUCTURES [690.43] |
| _____ EQUIPMENT GROUNDING CONDUCTOR (EGC) SHALL BE |
| CONTAINED IN SAME RACEWAY WHEN LEAVING VICINITY OF |
| ARRAY [690.43] |
| _____ EGC SIZED NO SMALLER THAN #14 AND NOT SMALLER |
| THAN LARGEST CURRENT CARRYING CONDUCTOR [250.122]. |
| _____ CHECK AC/DC IS BONDED AT INVERTER [690.C 1] |
| _____ CHECK EQUIPMENT GROUNDING CONDUCTORS ARE SIZED IN |
| ACCORDANCE WITH 690.45(A) 250.122 OR (B) WHEN NO GROUND |
| FAULT EGC SIZED TO TWO (2) TIMES THE TEMP AND CONDUIT |
| FILL CONDUCTOR AMPACITY. |
| _____ ARRAY GROUNDING ELECTRODE CONDUCTORS (GEC) NOT |
| SMALLER THAN #6 AND COMPLIES WITH 250.120(C) |
| _____ SYSTEMS WITH AC ONLY (MICRO INVERTERS) THE |
| GROUNDING ELECTRODE SYSTEM SHALL BE INSTALLED PER |
| [690.47(A) IN ACCORDANCE WITH [250.50 THRU 250.60] AND |
| [250.64] |
| _____ SYSTEMS WITH BOTH AC AND DC SHALL BE INSTALLED |
| PER [690.47 (C)(1) THRU (C)(8) AND SIZED PER 250.66 |
| (AC) 250.166 (DC) |
| _____ INSPECT PREMISES GROUNDING AS IT SERVES AS THE AC |
| GROUNDING FOR PV SYSTEMS [690.47 C 8] |
| _____ IF GROUND OR POLE MOUNT GROUNDING ELECTRODE |
| INSTALLED PER 250.52 AND WITHIN 6 FEET [690.47D |
| EXCEPTION 2]. |
| _____ CHECK ELECTRODE IS CONNECTING DIRECTLY TO FRAMES |
| AND STRUCTURES [690.47 D] |
| _____ IF BREAKS IN RAILS OF MOUNTING STRUCTURE, CHECK |
| FROM JUMPER [690.48] |
| _____ BONDING, GROUNDED FITTINGS AND/OR BUSHINGS SHALL |
| BE USED WITH METAL CONDUITS IF VOLTAGE IS OVER 250V DC |
| [250.97] |
| |
| DISCONNECTING MEANS |
| |
| _____ DC DISCONNECTS SHALL BE LISTED FOR DC OPERATION, |
| ARE NOT REQUIRED TO BE SUITABLE AS SERVICE EQUIPMENT |
| AND SHALL MEET [690.17]. GENERALLY, MARINE, AUTOMOTIVE |
| NOR TELECOMDEVICES ARE ACCEPTABLE AS THEY ARE NOT |
| SUITED FOR USE. |
| _____ DISCONNECTS SHALL BE READILY ACCESSIBLE EITHER ON |
| THE OUTSIDE OF THE BUILDING OR INSIDE NEAREST THE FIRST |
| POINT OF ENTRANCE [690.14(C)(1)] |
| _____ NOTE MANY UL 1741 LISTED INVERTERS HAVE INTERNAL |
| DC DISCONNECTS. INSPECT DC INPUT?S MAXIMUM CURRENT |
| [690.53] DOES NOT EXCEED DISCONNECT LISTING AS THE |
| DISCONNECT MAY BE A SEPARATELY MANUFACTURED PRODUCT |
| (EITHER BY THE INVERTER MANUFACTURE OR OTHERS). |
| |
| AC GRID CONNECTION |
| |
| _____ POINT OF CONNECTION, SUPPLY SIDE. AN ELECTRICAL |
| POWER PRODUCTION SOURCE CONNECTED SUPPLY SIDE OF THE |
| SERVICE DISCONNECTING MEANS AS PERMITTED IN 230.82 (6) |
| IS PERMITTED PER 705.12 (A) PERMITTING THE SUM OF THE |
| RATINGS OF ALL OVERCURRENT DEVICES CONNECTED TO ALL |
| POWER PRODUCTION SOURCES DO NOT EXCEED THE RATING OF |
| THE SERVICE. |
| _____ CIRCUIT BREAKER SHALL BE SUITABLE AS A BACKFEED |
| BREAKER IF INSTALLED ON THE LOAD SIDE OF THE SERVICE |
| DISCONNECTING MEANS ON THE PREMISES. NOTE: CIRCUIT |
| BREAKER MARKED ?LINE? AND ?LOAD? HAVE BEEN EVALUATED |
| FOR THE DIRECTION MARKED. CIRCUIT BREAKERS WITHOUT |
| ?LINE? AND ?LOAD? HAVE BEEN EVALUATED IN BOTH |
| DIRECTIONS. |
| _____ CHECK THE SUM OF THE AMPERE RATING OF THE |
| OVERCURRENT DEVICES IN CIRCUIT SUPPLYING POWER TO A |
| BUSBAR OR CONDUCTOR DO NOT EXCEED 120% OF THE RATING OF |
| THE BUSBAR AS CALCULATED IN [220.82 ~88] NEC 2008/11 |
| [705.12(D)(2)] |
| |
| APPROPRIATE SIGNS INSTALLED 690 VI - MARKINGS: |
| |
| _____ CHECK PROPER SIGN CONSTRUCTION 690.53 WITH |
| MARKINGS AS FOLLOWS: |
| 690.53 (1) RATED MAXIMUM POWER POINT CURRENT |
| 690.52 (2) RATED MAXIMUM POWER POINT VOLTAGE |
| 690.53 (3) MAXIMUM SYSTEM VOLTAGE (I.E. ARRAY MAX |
| VOLTAGE ? A CALCULATED VALUE 690.7) |
| 690.53 (4) SHORT CIRCUIT CURRENT (I.E. SEE 690.8(A) ? A |
| CALCULATED VALUE |
| 690.53 (5) MAXIMUM RATED OUTPUT CURRENT OF THE CHARGE |
| CONTROLLER (IF INSTALLED) |
| NOTE: NEC2011 690.53 CALLS FOR A PERMANENT LABEL. LABEL |
| SHALL BE ENGRAVED AND/OR SUNLIGHT RESISTANT (I.E. |
| STICKERS MAY NOT MEET THE CODE) |
| _____ THE INTERACTIVE SYSTEM (GRID TIED) POINT OF |
| INTERCONNECTION SHALL BE MARKED IN AN ACCESSIBLE |
| LOCATION AT THE POWER SOURCE DISCONNECTING MEANS WITH |
| THE RATED AC OUTPUT CURRENT AND NOMINAL AC VOLTAGE |
| [690.54]. |
| _____ IF ENERGY STORAGE IS EMPLOYED (I.E. BATTERIES) |
| THE ENERGY STORAGE SHALL ALSO BE MARKED WITH MAXIMUM |
| OPERATING VOLTAGE, INCLUDING ANY EQUALIZATION VOLTAGE |
| AND THE POLARITY OF THE GROUNDED CIRCUIT CONDUCTOR |
| [690.55]. |
| _____ CHECK FOR DIRECTORY I.E. A PERMANENT SIGN, PLAQUE |
| OF DIRECTORY DENOTING ALL ELECTRICAL POWER SOURCES ARE |
| POSTED AT A READILY ACCESSIBLE LOCATION PER [705.10] ON |
| OR IN THE PREMISES IDENTIFYING PV POWER SOURCE SYSTEM |
| ATTRIBUTES AT DC DISCONNECT [690.53(1~5)] |
| _____ FACILITIES WITH STAND ALONE SYSTEMS. ANY |
| STRUCTURE OR BUILDING WITH A PV POWER SYSTEM THAT IS |
| NOT CONNECTED TO THE GRID IS CONSIDERED STAND ALONE. |
| CHECK FOR A PERMANENT SIGN IDENTIFYING SERVICE |
| DISCONNECT AND PV DISCONNECTING MEANS PER [690.56, |
| 705.10] |
| |
| CHECK THAT EQUIPMENT RATINGS ARE CONSISTENT WITH |
| APPLICATION AND SIGNS: |
| _____ CHECK THAT INVERTER HAS A RATING AS HIGH AS MAX |
| VOLTAGE ON PV POWER SOURCE SIGN [690.53] |
| _____ CHECK THAT DC-SIDE OCPDS ARE DC RATED AT LEAST AS |
| HIGH AS MAX VOLTAGE ON SIGN |
| _____ CHECK THAT SWITCHES AND OCPDS ARE INSTALLED |
| ACCORDING TO MANUFACTURERS SPECIFICATIONS |
| |
| (I.E. MANY 600VDC SWITCHES NOW REQUIRE PASSING THROUGH |
| THE SWITCH POLES TWICE IN A SPECIFIC WAY TO PROTECT FOR |
| ARC FLASH AND BLAST). |
| |
| NOTE: ALL EQUIPMENT SHALL BE INSTALLED PER 110.3(B) |
| |
| _____ CHECK THAT INVERTER IS RATED FOR THE SITE AC |
| VOLTAGE SUPPLIED AND SHOWN ON THE AC POINT OF |
| CONNECTION SIGN [690.54] |
| _____ CHECK THAT OCPD CONNECTED TO THE AC OUTPUT OF THE |
| INVERTER IS RATED AT LEAST 125% OF MAXIMUM CURRENT ON |
| SIGN, AND IS NO LARGER THAN THE MAXIMUM OCPD ON THE |
| INVERTERLISTING LABEL [690.8 A3, B1] |
| |
| |
| |