Plan Review Notes
Plan Review Notes For Permit 15040374
Permit Number 15040374
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-21 13:03:094/21/2015
 PROJECT: PHOTOVOLTAIC SYSTEM 3121 WASHINGTON RD
 PERMIT#: 15040374
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE SITE PLAN INCLUDING THE FOLLOWING: WPB
 AMENDMENTS TO THE FBC 107.3.2
 THE LOCATION HOUSE ON THE PROPERTY.
 THE LOCATION OF THE PHOTOVOLTAIC DC DISCONNECT /
 INVERTER ON THE HOUSE.
 THE LOCATION OF THE ELECTRICAL UTILITY METER ON THE
 HOUSE.
 THE LOCATION OF THE ELECTRICAL SERVICE PANEL ON OR IN
 THE HOUSE.
  
 2) PROVIDE ALL SIGNAGE REQUIRED BY THE NEC 690
  
 3) INDICATE THE LOCATION OF EACH OF THE REQUIRED SIGNS
 IN RELATION TO THE NEW PHOTOVOLTAIC EQUIPMENT AND THE
 EXISTING ELECTRICAL EQUIPMENT. NEC 690
  
 4) PROVIDE MANUFACTURER PRODUCT APPROVALS ON EQUIPMENT
 INDICATING COMPLIANCE WITH LISTING REQUIRMENTS. NEC
 690,4(D)
  
 5) INDICATE A GROUNDING ELECTRODE DETAIL AT THE
 ELECTRICAL SERVICE AND INDICATE HOW THE SOLAR ARRAY
 GROUNDING ELECTRODE CONNECTS TO THE ELECTRICAL SYSTEM
 GROUNDING ELECTRODE SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  