Plan Review Notes For Permit 15040362 |
Permit Number |
15040362 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-13 04:26:44 | 1) SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL GAS | | APPLIANCES/EQUIPMENT. ALL APPLIANCES/EQUIPMENT SHALL BE | | LISTED AND LABELED PER THE 2010 FBCR SEC.G2404.3. | | 2) INDICATE THE DELIVERY PRESSURE ( PSI ) OF THE GAS ON | | THE PLANS. 2010 FBCR SEC. G2413.1. | | 3) INDICATE THE CORRESPONDING EHD FOR EACH SIZE OF THE | | CSST PIPING USED. | | 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE | | DRYER. COMPLY WITH 2010 FBCR SEC.G2407.5.1 OR | | G2407.5.2. | | 5) SUBMIT A FLOOR PLAN THAT IS CLEAR AND LEGIBLE. THE | | ONE SUBMITTED HAS A FEW LARGE BLACK LINES ACROSS THE | | PAGE MAKING IT DIFFICULT TO SEE THINGS. WPB AMEND. TO | | 2010 FBCR 107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|