Notes |
Date |
Text |
2015-04-29 17:38:54 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | FBC-R 301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS | | THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL | | LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS, | | FLOOD LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE. | | THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN | | ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL | | RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH | | THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL | | LOADS FROM THEIR POINT OF ORIGIN THROUGH THE | | LOAD-RESISTING ELEMENTS TO THE FOUNDATION. | | | | 1) SPECIFY THE SIZE OF THE HEADER THAT WILL CARRY THE 2 | | X 8 RAFTERS AND BE ATTACHED TO THE 4 X 4 POSTS. | | | | 2) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR | | THE 4 X 4 POSTS TO THE 10 X 10 X 12 CONCRETE PADS AND | | TO THE HEADER BEAM. | | | | 3) SPECIFY HOW THE DOUBLE 2 X 8 P.T. LEDGER WILL BE | | ATTACHED TO THE EXISTING STRUCTURE. | | | | 4) THE DESIGN CRITERIA SPECIFIES ASCE 7 - 02 WHICH IS | | NOT THE EDITION THAT IS REFERENCED BY THE 2010 FBC. | | UPDATE TO ASCE 7 - 10. THE OCCUPANCY TYPE IS R-3, NOT | | TYPE V. | | | | |
|