Plan Review Notes
Plan Review Notes For Permit 15040359
Permit Number 15040359
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-29 17:38:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 FBC-R 301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS
 THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS,
 FLOOD LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE.
 THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
  
 1) SPECIFY THE SIZE OF THE HEADER THAT WILL CARRY THE 2
 X 8 RAFTERS AND BE ATTACHED TO THE 4 X 4 POSTS.
  
 2) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR
 THE 4 X 4 POSTS TO THE 10 X 10 X 12 CONCRETE PADS AND
 TO THE HEADER BEAM.
  
 3) SPECIFY HOW THE DOUBLE 2 X 8 P.T. LEDGER WILL BE
 ATTACHED TO THE EXISTING STRUCTURE.
  
 4) THE DESIGN CRITERIA SPECIFIES ASCE 7 - 02 WHICH IS
 NOT THE EDITION THAT IS REFERENCED BY THE 2010 FBC.
 UPDATE TO ASCE 7 - 10. THE OCCUPANCY TYPE IS R-3, NOT
 TYPE V.
  
  