2015-04-24 17:03:53 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15040340 |
| ADD: 1701 S. FLAGLER DR. SUITE # 1006 |
| CONT: KASICA INTERIOR CONSTRUCTION INC./ CARPENTRY |
| CONTRACTOR |
| TEL: (561) |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE JUNE 01, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE. |
| |
| 1ST REVIEW |
| DATE: FRI. APRIL 24/ 2015 |
| ACTION: DENIED |
| |
| 1) KASICA INTERIOR CONSTRUCTION INC./ CARPENTRY |
| CONTRACTOR IS NOT LICENSE TO DO HIS WORK. SPECIALTY |
| CONTRACTOR STANDARDS |
| "SPECIALTY CONTRACTORS" ARE THOSE WHO CAN QUALIFY WITH |
| A MINIMUM OF THREE YEARS EXPERIENCE, 1-1/2 YEARS OF |
| WHICH MUST BE IN A SUPERVISORY CAPACITY, WHO SPECIALIZE |
| IN ONE OR MORE OF THE CRAFTS OF THE BUILDING |
| CONSTRUCTION AND RELATED CONTRACTING TRADES. A |
| CERTIFIED SPECIALTY CONTRACTOR SHALL BE ABLE TO |
| SUBCONTRACT ANY WORK INCIDENTAL TO THE WORK OF THEIR |
| SPECIALTY CERTIFICATION. INCIDENTAL-FOR THE PURPOSE OF |
| THIS DOCUMENT INCIDENTAL SHALL MEAN WORK OF A NATURE |
| EXPECTED TO BE REQUIRED IN THE PERFORMANCE OF A |
| CONTRACT. SUCH WORK SHALL NOT BE THE PRIMARY PURPOSE OF |
| THE CONTRACT NOR EXCEED 49% OF THE TOTAL PRIME |
| CONTRACT. |
| |
| CARPENTRY CONTRACTORS ARE THOSE WHO HAVE THE KNOWLEDGE |
| AND SKILL TO INSTALL, MAINTAIN, REPAIR, ALTER OR EXTEND |
| ANY WOOD PRODUCTS AND THEIR REPLACEMENT PRODUCTS IN OR |
| ON A BUILDING INCLUDING, BUT NOT LIMITED TO, ROUGH |
| FRAMING, STRUCTURAL AND NONSTRUCTURAL TRUSSES, |
| CONVENTIONAL RAFTERS, METAL FRAMING, AND WOODEN |
| FENCING; ALSO INCLUDES THE WORK OF THE CARPENTRY-FINISH |
| CONTRACTOR. |
| |
| 2) KASICA INTERIOR CONSTRUCTION INC./ CARPENTRY |
| CONTRACTOR IS NOT LICENSE TO DESIGN IN HIGH RISE |
| CONSTRUCTION. 107.3.4.3 CERTIFICATIONS BY CONTRACTORS |
| AUTHORIZED UNDER THE PROVISIONS OF SECTION 489.115 |
| FLORIDA STATUTES, SHALL BE CONSIDERED EQUIVALENT TO |
| SEALED PLANS AND SPECIFICATIONS BY A PERSON LICENSED |
| UNDER CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 |
| FLORIDA STATUTES, BY LOCAL ENFORCEMENT AGENCIES FOR |
| PLANS REVIEW FOR PERMITTING PURPOSES RELATING TO |
| COMPLIANCE WITH THE WIND-RESISTANCE PROVISIONS OF THE |
| CODE OR ALTERNATE METHODOLOGIES APPROVED BY THE FLORIDA |
| BUILDING COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. |
| LOCAL ENFORCEMENT AGENCIES MAY RELY UPON SUCH |
| CERTIFICATION BY CONTRACTORS THAT THE PLANS AND |
| SPECIFICATIONS SUBMITTED CONFORM TO THE REQUIREMENTS OF |
| THE CODE FOR WIND RESISTANCE. UPON GOOD CAUSE SHOWN, |
| LOCAL GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT |
| OR REJECT PLANS SEALED BY PERSONS LICENSED UNDER |
| CHAPTERS 471,481 OR 489, FLORIDA STATUTES. |
| |
| 3)SHEET 1.1 DESIGN PARAMETERS. |
| 3A) THE WIND DESIGN IS DESIGNED TO THE WRONG ASCE 7-05. |
| THE CURRENT CODE REQUIRES HIGH-RISE STRUCTURES TO BE |
| DESIGNED TO ASCE 7-10. 2010 FBC-B 1609.1.1. |
| |
| 3B) THE PLANS INDICATE THE PLANS WERE DESIGNED TO THE |
| 2010 FBC RESIDENTIAL CODE, THE RESIDENTIAL CODE IS FOR |
| 1 & 2 FAMILY DWELLINGS. CONDOMINIUM ARE COMMENRCIAL AND |
| DESIGNED UNDER THE 2010 FBC-BUILDING. |
| |
| 3C) OCCUPANCY TYPE STATES R3 / CONDOMINIUM. PLEASE |
| REVIEW THE 2010 FBC-B SECTION 310 R-2 IS CONDOMINIUM/ |
| APARTMENT HOUSES. |
| |
| 4) THE WIND DESIGN CRITERIA ALSO STATES THE WIND |
| EXPOSURE TO BE A "C" EXPOSURE. 2010 FBC-B 1609.1.1 |
| DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE |
| WITH 1609.4.3 & ASCE 7-10. EXPOSURE D. EXPOSURE D SHALL |
| APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS DEFINED BY |
| SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION |
| FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 |
| TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. |
| EXPOSURE D SHALL EXTEND INLAND FROM THE SHORELINE FOR A |
| DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE HEIGHT OF |
| THE BUILDING, WHICHEVER IS GREATER FROM AN EXPOSURE D |
| CONDITION AS DEFINED IN THE PREVIOUS SENTENCE. |
| |
| 5) THE SUBMITTED PRODUCT APPROVALS FOR SLIDDING GLASS |
| DOORS ARE NOT CIRCLED FOR HEIGHT, WIDTH, TYPE OF |
| GLAZING, TRACK HEIGHT, TYPE OF ANCHOR AND ASSOCIATED |
| PRESSURES IF REINFORCING IS REQUIRED IN STYLES ETC... |
| 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS |
| FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL |
| ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE |
| WITH THIS CODE. THE CONSTRUCTION DOCUMENTS SHALL |
| PROVIDE DETAILS OF THE EXTERIOR WALL ENVELOPE AS |
| REQUIRED. |
| |
| 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 7) THE PLANS INDICATE THE FLOORS ARE GOING TO BE |
| REPLACED AND NEEDING SOUND INSULATION, PLEASE COMPLY |
| WITH: |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| |
| 7A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 7B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 7C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 703.4 NONCOMBUSTIBILITY TESTS. |
| THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| |
| 703.4.1 ELEMENTARY MATERIALS. |
| MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| IN ACCORDANCE WITH ASTM E 136. |
| |
| 703.4.2 COMPOSITE MATERIALS. |
| MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 SHALL BE ACCEPTABLE AS |
| NONCOMBUSTIBLE MATERIALS. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| |
| |