2015-06-03 17:17:44 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) THE SCOPE OF WORK IS TO ADD A METER AND RELOCATE A | | PANEL IN UNIT #3 ONLY. | | | | 2) SMOKE DETECTORS REQUIRED. WHEN ALTERATIONS, REPAIRS, | | OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR | | MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING | | DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE | | EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW | | DWELLINGS. FBC-RESIDENTIAL 314 AND 315. | | | | 3) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE | | PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT | | TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF | | SUCH EQUIPMENT. NEC 110.26 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|