Plan Review Notes
Plan Review Notes For Permit 15040317
Permit Number 15040317
Review Stop E
Sequence Number 3
Notes
Date Text
2015-05-18 11:33:055/18/2015 THE OWNER CAME IN WITH AN ELECTRICIAN. THE
 ELECTRICIAN IS NOT THE QUALIFIER. I EXPLAINED TO BOTH
 OF THEM THAT I NEEDED TO SPEAK WITH THE QUALIFIER. THEY
 WERE BOTH ADVISED THE PROJECT FALLS OUTSIDE OF THE
 SCOPE OF THE CONTRACTOR?S LICENSE AND AN ENGINEER NEEDS
 TO BE INVOLVED. ONE PART OF THE SCOPE IS TO ADD A METER
 AND A MAIN IN THE ELECTRICAL ROOM TO FEED ONE OF THE
 SIX UNITS IN A SIX UNIT APARTMENT COMPLEX. I ASKED FOR
 A DESIGN OF THE ELECTRICAL SERVICE AND EXPLAINED THE
 STATUTORY LIMIT TO THE QUALIFIER?S SCOPE AND THEREFORE
 THE NEED FOR AN ENGINEERED DRAWING FOR THIS WORK
  
 FL SS 471.003 (H) ANY ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE
 PRACTICE INCLUDES THE DESIGN AND FABRICATION OF
 ELECTRICAL PLUMBING, AIR CONDITIONING, OR MECHANICAL
 SYSTEMS RESPECTIVELY WHICH SHE OR HE INSTALLS BY VIRTUE
 OF A LICENSE ISSUED UNDER CHAPTER 489, UNDER PART I OF
 CHAPTER 553 OR UNDER ANY SPECIAL ACT OR ORDINANCE WHEN
 WORKING ON ANY CONSTRUCTION PROJECT WHICH:
 1) REQUIRES AN ELECTRICAL OR PLUMBING OR AIR
 CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE OF
 $50,000.00 OR LESS; AND
 2A) REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600AMPS
 (240VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM
 OR 800 AMPERES (240VOLTS) OR LESS ON A COMMERCIAL OR
 INDUSTRIAL ELECTRICAL SYSTEM;
  