Plan Review Notes
Plan Review Notes For Permit 15040316
Permit Number 15040316
Review Stop M
Sequence Number 2
Notes
Date Text
2015-08-13 07:43:56MECHANICAL APPROVED WITH EXCEPTION.
 8/13/15
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 1) REVISE THE AC PLAN TO SHOW THE TOTAL BALANCED 525
 CFM AIR DISTRIBUTION, AND SHOW THE RETURN DUCT SIZES.
 2) PROVIDE A CONDENSER TIE DOWN DETAIL WITH LEGIBLE
 NOTES AND DETAILS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  