2015-06-01 19:22:00 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS SPECIFY THAT THE EXPOSURE CATEGORY FOR |
| THIS PROJECT IS B. THERE IS A CEMETARY TO THE WEST OF |
| THIS LOCATION THAT IS SURFACE ROUGHNESS C. FOR THE |
| DISTANCE OF 1500 FT TO THE WEST THE PREVAILING SURFACE |
| ROUGHNESS C, THEREFORE THIS PROJECT IS EXPOSURE C. |
| FBC-R 301.2.1.4.3 |
| |
| 2) A NOTE ON THE FOUNDATION PLAN STATES THAT THE |
| CONCRETE SLAB WAS POURED UNDER PREVIOUS PERMIT |
| #04070391. THAT PERMIT WAS NEVER APPROVED OR ISSUED AND |
| THEREFORE NO INSPECTIONS WERE DONE ON THE FOUNDATION. |
| THERE WAS A PERMIT (99121464) TO INSTALL A 4" THICK |
| PATIO SLAB WITH THE DIMENSIONS OF 25' X 34' - 3", WHICH |
| ARE THE DIMENSIONS OF THE PROPOSED ADDITION. THIS 4" |
| PATIO SLAB WILL NOT BE ADEQUATE TO SUPPORT THE EXTERIOR |
| WALLS OF THE ADDITION AND THE TERMITE PROTECTION |
| REQUIREMENTS WOULD NEED TO BE ADDRESSED. FBC 107.2.1, |
| FBC-R 301.1 AND 318 |
| |
| 3) THE SLEEPING ROOM WINDOWS ARE REQUIRED COMPLY WITH |
| FBC-R 310 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS. |
| BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM |
| SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND |
| RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE |
| SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS |
| SHALL BE REQUIRED IN EACH SLEEPING ROOM. WHERE |
| EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY |
| SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES |
| (1118 MM) ABOVE THE FLOOR. WHERE A DOOR OPENING HAVING |
| A THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES |
| AS AN EMERGENCY ESCAPE AND RESCUE OPENING AND IS |
| PROVIDED WITH A BULKHEAD ENCLOSURE, THE BULKHEAD |
| ENCLOSURE SHALL COMPLY WITH SECTION R310.3. THE NET |
| CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL |
| BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY |
| ESCAPE AND RESCUE OPENING FROM THE INSIDE. EMERGENCY |
| ESCAPE AND RESCUE OPENINGS WITH A FINISHED SILL HEIGHT |
| BELOW THE ADJACENT GROUND ELEVATION SHALL BE PROVIDED |
| WITH A WINDOW WELL IN ACCORDANCE WITH SECTION R310.2. |
| EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL OPEN |
| DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT |
| OPENS TO A PUBLIC WAY. |
| FBC-R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY ESCAPE |
| AND RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR |
| OPENING OF 5.7 SQUARE FEET (0.530 M2). |
| EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM |
| NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2). |
| |
| FBC-R310.1.2 MINIMUM OPENING HEIGHT. |
| THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES |
| (610 MM). |
| |
| FBC-R310.1.3 MINIMUM OPENING WIDTH. |
| THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES |
| (508 MM). |
| |
| |
| 4) THE FOOTING REINFORCING BARS AND SLAB OF THE NEW |
| ADDITION SHOULD BE DOWELED INTO THE EXISTING FOOTINGS |
| AND SLAB TO PREVENT UNEVEN SETTLEMENT. FBC 107.2.1 |
| |
| 5) THE NOTE ON THE EXTERIOR WALL SECTION ON SHEET 4 |
| CALLS FOR 3/4" STUCCO OVER PAPER-BACKED METAL LATH ON A |
| CONCRETE BLOCK EXTERIOR WALL. THIS NOTE APPEARS TO BE |
| IN ERROR. CLARIFY. FBC 107.2.1 |
| |
| 6) THE EXTERIOR WALL SECTION ON SHEET 4 SPECIFIES 6" |
| THICK BATT INSULATION WITH AN R30 INSULATION VALUE. |
| THERE IS NO 6" BATT INSULATION WITH AN R-30 VALUE. FBC |
| 107.2.1 |
| |
| 7) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION |
| SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER |
| CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORM |
| 405. |
| |
| 8) SPECIFY THE R-VALUE FOR THE EXTERIOR WALL INSULATION |
| THAT WILL BE USED ON THE PLANS. FBC 107.2.1 |
| |
| 9) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE |
| FOLLOWING LOCATIONS: |
| 1. IN EACH SLEEPING ROOM. |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| |
| 10) THE STRUCTURAL OVERHANG DETAIL AT THE GABLE END |
| RAKED BEAM DOES NOT SHOW COMPLIANCE WITH WINDLOAD |
| UPLIFT REQUIREMENTS. SPECIFY THE LENGTH OF THE |
| OVERHANG. FBC-R 301.1 |
| |
| 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE |
| ASPHALT SHINGLE AND WINDOWS. |
| |
| 12) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE |
| VALUATION OF $50,000.00 APPEARS TO BE LOW. SUBMIT A |
| COPY OF THE SIGNED CONTRACT. |
| |