2015-04-25 14:30:08 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 15040273 |
| W. P. B. PERMIT: 12050519 |
| ADD: 4748 FRED GLADSTONE DR. |
| CONT: THE WEITZ CO. |
| TEL: ( |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUNDAY APRIL 26/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEETS 000-G1.02 & 018-E-A101 IN STAIRWELL # 1 BOTH |
| INDICATE A NOTE PROVIDE 2 HOUR SHAFT AND A 2 HOUR |
| ACCESS PANEL. PLEASE PROVIDE WHAT THIS (2) HOUR FIRE |
| RATED ACCESS PANEL WILL BE USED FOR? PLEASE SEE THE |
| ONLY ITEMS THAT ARE ALOUD IN THE EXIT STAIRWELL, |
| ASSUMING THIS IS AN REQUIRED EXIT? 2010 FBC-B 1022.4 |
| PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN |
| EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 713. THERE SHALL BE NO PENETRATIONS OR |
| COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| BETWEEN ADJACENT EXIT ENCLOSURES. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |