2015-04-25 14:30:08BUILDING PLAN REVIEW
 W. P. B. REVISION: 15040273
 W. P. B. PERMIT: 12050519
 ADD: 4748 FRED GLADSTONE DR.
 CONT: THE WEITZ CO.
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY APRIL 26/ 2015
 ACTION: DENIED
  
 1) SHEETS 000-G1.02 & 018-E-A101 IN STAIRWELL # 1 BOTH
 INDICATE A NOTE PROVIDE 2 HOUR SHAFT AND A 2 HOUR
 ACCESS PANEL. PLEASE PROVIDE WHAT THIS (2) HOUR FIRE
 RATED ACCESS PANEL WILL BE USED FOR? PLEASE SEE THE
 ONLY ITEMS THAT ARE ALOUD IN THE EXIT STAIRWELL,
 ASSUMING THIS IS AN REQUIRED EXIT? 2010 FBC-B 1022.4
 PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN
 EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER