Plan Review Notes
Plan Review Notes For Permit 15040264
Permit Number 15040264
Review Stop B
Sequence Number 2
Notes
Date Text
2015-04-21 09:36:49RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
  
 FLAT ROOF NOA 11-0119.09 SUBMITTED:
  
 1- SELECTED ASSEMBLY FROM PAGE 32 OF 41 CAN NOT BE
 USED. IT IT'S LIMITED BY GENERAL LIMITATION #9. SEE
 PAGE 33 OF 41. GENERAL LIMITATION #9 DOESN'T ALLOW
 RATIONAL ANALYSIS OR EXTRAPOLATION. (RAS 117
 CALCULATIONS). SEE GENERAL LIMITATION #9 ON LAST PAGE
 OF NOA. NEED TO SELECT AN ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #7, WHICH ALLOWS RATIONAL ANALYSIS
 OR EXTRAPOLATION TO MEET THE DESIGN PRESSURES OF SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. NOTE:
 PRESCRIPTIVE NAIL ENHANCING SUBMITTED IS NOT ALLOWED
 BECAUSE RAS 150 IS NOT ADOPTED BY THE CITY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT