Plan Review Notes For Permit 15040264 |
Permit Number |
15040264 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-21 09:36:49 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | | | FLAT ROOF NOA 11-0119.09 SUBMITTED: | | | | 1- SELECTED ASSEMBLY FROM PAGE 32 OF 41 CAN NOT BE | | USED. IT IT'S LIMITED BY GENERAL LIMITATION #9. SEE | | PAGE 33 OF 41. GENERAL LIMITATION #9 DOESN'T ALLOW | | RATIONAL ANALYSIS OR EXTRAPOLATION. (RAS 117 | | CALCULATIONS). SEE GENERAL LIMITATION #9 ON LAST PAGE | | OF NOA. NEED TO SELECT AN ASSEMBLY THAT IS LIMITED BY | | GENERAL LIMITATION #7, WHICH ALLOWS RATIONAL ANALYSIS | | OR EXTRAPOLATION TO MEET THE DESIGN PRESSURES OF SEC. | | R301.1 OF 2010 FBC-RESIDENTIAL. | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. NOTE: | | PRESCRIPTIVE NAIL ENHANCING SUBMITTED IS NOT ALLOWED | | BECAUSE RAS 150 IS NOT ADOPTED BY THE CITY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|