Text |
2015-07-08 11:27:25 | CONTRACTOR HAS NOT ADDRESSED ORIGINAL REVIEW DEFICIENCY |
| COMMENTS. PLEASE READ AND COMPLY WITH ALL THE |
| FOLLOWING: |
| |
| NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES |
| THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A |
| CODE VIOLATION. |
| |
| 1) INDICATE REQUIRED EXIT SIGNS ON THE FLOOR PLAN. |
| ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY |
| VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| REACH THE EXIT IS NOT READILY APPARENT TO THE |
| OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1 |
| 2) INDICATE REQUIRED EMERGENCY ILLUMINATION. EMERGENCY |
| LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO |
| THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT, |
| SUCH AS THE BURNING OUT OF A LAMP CANNOT LEAVE IN TOTAL |
| DARKNESS ANY SPACE THAT REQUIRES EMERGENCY |
| ILLUMINATION. NEC 700.16 |
| 3) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. THE |
| BRANCH CIRCUIT FEEDING THE EMERGENCY LIGHTING SHALL BE |
| THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. NEC 700.12 |
| 4) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT |
| MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
2015-07-01 19:37:43 | I TRIED CONTACTING MR. RAWLS FOR FURTHER EXPLANATION OF |
| HIS DESIGN BUT VM WAS FULL. I DEFERRED THIS BACK TO |
| DHAYES. |