2015-04-09 15:42:511) INDICATE REQUIRED EXIT SIGNS ON THE FLOOR PLAN.
 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1
 2) INDICATE REQUIRED EMERGENCY ILLUMINATION. EMERGENCY
 LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO
 THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT,
 SUCH AS THE BURNING OUT OF A LAMP CANNOT LEAVE IN TOTAL
 DARKNESS ANY SPACE THAT REQUIRES EMERGENCY
 ILLUMINATION. NEC 700.16
 3) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. THE
 BRANCH CIRCUIT FEEDING THE EMERGENCY LIGHTING SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12
 4) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  