Plan Review Notes For Permit 15040249 |
Permit Number |
15040249 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-09 14:29:54 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314 AND 315. | | 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 | | 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES | | INSTALLED IN THE KITCHEN SHALL HAVE GROUND FAULT | | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. NEC | | 210.8(6) |
|