Plan Review Notes For Permit 15040220 |
Permit Number |
15040220 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-19 14:44:18 | MECHANICAL PROVISO: | | | | 1) OUTSIDE AIR SUPPLY FOR AHU-1 SHALL CONNECT TO THE | | RETURN AIR PLENUM, NOT THE SUPPLY PLENUM AS SHOWN ON | | THE PLAN. | | | | CHRISTOPHER COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|