Plan Review Notes For Permit 15040220 |
Permit Number |
15040220 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-19 12:32:13 | PROVISO: | | | | HALL AND FOYER RECEPTACLES ARE REQUIRED. NEC 210.52(H) | | | | AN ELECTRICAL GROUNDING SYSTEM IS REQUIRED. NEC 250.24 | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH | | CIRCUITS SUPPLYING OUTLETS. NEC 210.12 | | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. | | NEC 210.11 (C) (3) | | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE DINING AREA | | OUTLETS. NEC 210.52(B) (1) | | | | A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE | | GROUND. NEC 250.94 | | | | | | |
|