Plan Review Notes
Plan Review Notes For Permit 15040220
Permit Number 15040220
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-20 11:23:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE COMPONENT AND CLADDING PRESSURES ON S.01 ARE FOR
 A TWO STORY STRUCTURE WITH A 23'-0" MEAN ROOF HEIGHT.
 THIS PROJECT IS FOR A ONE STORY STRUCTURE WITH A 14'-5"
 MEAN ROOF HEIGHT PER THE ELEVATION DRAWINGS. FBC-R
 301.2.1
  
 2) THE MEAN ROOF HEIGHT IS 15'-4" ON THE NORTH
 ELEVATION ON SHEET A.05 AND IT IS 14'-5" ON THE OTHER
 ELEVATIONS. CLARIFY. FBC 107.2.1
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE 5' MASONRY WALL
 AND GATES AT THE REAR OF THE STRUCTURE. FBC-R 301.2.1
  
 4) SPECIFY THE COMPONENT AND CLADDING DESIGN PRESSURES
 FOR THE 10 : 12 SLOPED AND 1/2" : 12 FLAT ROOF AREAS ON
 THE PLANS. FBC-R 301.2.1
  
 5) IDENTIFY THE TYPE OF WINDOW ( SINGLE HUNG, FIXED,
 HORIZONTAL SLIDING, ETC. ) FOR EACH OPENING ON THE
 PLANS. FBC 107.2.1
  
 6) SPECIFY THE SIZES OF THE DOOR SIDELITES AND OF EACH
 WINDOW WHEN MULTIPLES ARE INSTALLED IN ONE OPENING AS
 IN THE FAMILY ROOM. FBC 107.2.1
  
 7) FBC-R 403.1.4, AS WELL AS, THE SOIL REPORT REQUIRES
 THE BOTTOM OF FOOTINGS TO BE A MINIMUM OF 12" BELOW
 FINAL GRADE. DETAIL 1 ON S.03 FOR THE 18" DEEP FOOTING
 WILL NEED TO BE REVISED SO THAT THE 6" ABOVE GRADE IS
 TO THE FINISHED FLOOR RATHER THAN THE 1-1/2" BLOCK
 RECESS.
  
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 OUTDOOR GRILL AND HOOD WHICH INDICATES THAT IT IS
 LISTED FOR USE ON A COVERED PORCH WITH ONLY ONE SIDE
 OPEN TO THE EXTERIOR. FBC-R G2406.1
  
 9) SUBMIT THE CURRENT EVALUATION REPORT FOR THE SPRAY
 FOAM INSULATION THAT WILL BE USED. FBC-R 316
  
 10) SOME OF THE WINDOWS APPEAR TO BE SINGLE HUNG
 WINDOWS AND THERE WAS NOT A PRODUCT APPROVAL SUBMITTED
 FOR THEM. A PRODUCT APPROVAL WAS SUBMITTED FOR
 HORIZONTAL SLIDING WINDOWS (NOA NO.11-1031.04), BUT
 THERE DOES NOT APPEAR TO BE ANY OF THESE. PLEASE
 CLARIFY. DCA RULE 9N-3
  
 11) SPECIFY THE METHOD OF ATTACHMENT FROM THOSE LISTED
 IN NOA NO. 13-0723.05 THAT WILL BE USED TO INSTALL THE
 CONCRETE ROOF TILE AND PROVIDE ADEQUATE RESISTANCE TO
 THE OVERTURN MOMENT. FBC-R 301.2.1 ( NOTE: IF AN
 ADHESIVE WILL BE USED, SUBMIT IT'S PRODUCT APPROVALS.)
  
 12) SPECIFY THE APPROVED ASSEMBLY AND MAXIMUM DESIGN
 PRESSURE FROM NOA NO. 11-0119.09 ( FIRESTONE MODIFIED
 BITUMEN ROOF SYSTEM) THAT WILL BE INSTALLED. SUBMIT
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING. FBC-R 301.2.1
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  