Date |
Text |
2015-05-20 11:23:06 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE COMPONENT AND CLADDING PRESSURES ON S.01 ARE FOR |
| A TWO STORY STRUCTURE WITH A 23'-0" MEAN ROOF HEIGHT. |
| THIS PROJECT IS FOR A ONE STORY STRUCTURE WITH A 14'-5" |
| MEAN ROOF HEIGHT PER THE ELEVATION DRAWINGS. FBC-R |
| 301.2.1 |
| |
| 2) THE MEAN ROOF HEIGHT IS 15'-4" ON THE NORTH |
| ELEVATION ON SHEET A.05 AND IT IS 14'-5" ON THE OTHER |
| ELEVATIONS. CLARIFY. FBC 107.2.1 |
| |
| 3) PROVIDE STRUCTURAL DETAILS FOR THE 5' MASONRY WALL |
| AND GATES AT THE REAR OF THE STRUCTURE. FBC-R 301.2.1 |
| |
| 4) SPECIFY THE COMPONENT AND CLADDING DESIGN PRESSURES |
| FOR THE 10 : 12 SLOPED AND 1/2" : 12 FLAT ROOF AREAS ON |
| THE PLANS. FBC-R 301.2.1 |
| |
| 5) IDENTIFY THE TYPE OF WINDOW ( SINGLE HUNG, FIXED, |
| HORIZONTAL SLIDING, ETC. ) FOR EACH OPENING ON THE |
| PLANS. FBC 107.2.1 |
| |
| 6) SPECIFY THE SIZES OF THE DOOR SIDELITES AND OF EACH |
| WINDOW WHEN MULTIPLES ARE INSTALLED IN ONE OPENING AS |
| IN THE FAMILY ROOM. FBC 107.2.1 |
| |
| 7) FBC-R 403.1.4, AS WELL AS, THE SOIL REPORT REQUIRES |
| THE BOTTOM OF FOOTINGS TO BE A MINIMUM OF 12" BELOW |
| FINAL GRADE. DETAIL 1 ON S.03 FOR THE 18" DEEP FOOTING |
| WILL NEED TO BE REVISED SO THAT THE 6" ABOVE GRADE IS |
| TO THE FINISHED FLOOR RATHER THAN THE 1-1/2" BLOCK |
| RECESS. |
| |
| 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| OUTDOOR GRILL AND HOOD WHICH INDICATES THAT IT IS |
| LISTED FOR USE ON A COVERED PORCH WITH ONLY ONE SIDE |
| OPEN TO THE EXTERIOR. FBC-R G2406.1 |
| |
| 9) SUBMIT THE CURRENT EVALUATION REPORT FOR THE SPRAY |
| FOAM INSULATION THAT WILL BE USED. FBC-R 316 |
| |
| 10) SOME OF THE WINDOWS APPEAR TO BE SINGLE HUNG |
| WINDOWS AND THERE WAS NOT A PRODUCT APPROVAL SUBMITTED |
| FOR THEM. A PRODUCT APPROVAL WAS SUBMITTED FOR |
| HORIZONTAL SLIDING WINDOWS (NOA NO.11-1031.04), BUT |
| THERE DOES NOT APPEAR TO BE ANY OF THESE. PLEASE |
| CLARIFY. DCA RULE 9N-3 |
| |
| 11) SPECIFY THE METHOD OF ATTACHMENT FROM THOSE LISTED |
| IN NOA NO. 13-0723.05 THAT WILL BE USED TO INSTALL THE |
| CONCRETE ROOF TILE AND PROVIDE ADEQUATE RESISTANCE TO |
| THE OVERTURN MOMENT. FBC-R 301.2.1 ( NOTE: IF AN |
| ADHESIVE WILL BE USED, SUBMIT IT'S PRODUCT APPROVALS.) |
| |
| 12) SPECIFY THE APPROVED ASSEMBLY AND MAXIMUM DESIGN |
| PRESSURE FROM NOA NO. 11-0119.09 ( FIRESTONE MODIFIED |
| BITUMEN ROOF SYSTEM) THAT WILL BE INSTALLED. SUBMIT |
| SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED |
| FASTENING. FBC-R 301.2.1 |
| |
| 13) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| ADDRESSED. |
| |
| |
| |