Plan Review Notes
Plan Review Notes For Permit 15040207
Permit Number 15040207
Review Stop B
Sequence Number 3
Notes
Date Text
2015-04-20 10:37:56RESIDENTIAL (R3) ROOFING, THIRD BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- NOA SUBMITTED IS FOR INSULATED ASSEMBLIES ONLY.
 SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
 NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY
 GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN
 PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE
 GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 12-0418.02 SUBMITTED. NED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF
 2010 FBC-RESIDENTIAL.
  
 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT