2015-04-13 17:36:05RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- I REVIEWED THE PROPOSED ASSEMBLY W-10 FROM FLORIDA
 PRODUCT APPROVAL FL2920-R8. THIS ASSEMBLY IS GOOD FOR
 -85PSF. ACCORDING TO NOTE # 5 ON PAGE 1 OF 6 OF
 FL2920-R8 THIS ASSEMBLY CAN NOT BE USED BECAUSE IT
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED FOR THIS
 HOUSE AND RATIONAL ANALYSIS IS NOT ALLOWED. THIS HOUSE
 IS LOCATED IN EXPOSURE D. THE DESIGN PRESSURES FOR THE
 PERIMETER AND CORNER AREAS ARE HIGHER THAN -85PSF.
  
 2- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  