2015-04-07 06:15:29 | 1) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION |
| OF THE EXISTING WATER HEATER. WHAT WILL BE DONE WITH |
| THE EXISTING PLUMBING AND ELECTRIC? WPB AMEND. TO 2010 |
| FBC SEC. 107.2.1. |
| 2) INDICATE THE OCCUPANCY OF THIS SPACE? WHAT TYPE OF |
| BUSINESS IS CURRENTLY OCCUPYING THIS SPACE? FBC |
| SEC.302. |
| 3) INDICATE ON THE PLANS WHAT THESE SINKS WILL BE USED |
| FOR? WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 4) WHERE IS THE VENT FOR THE EXISTING SINK? WPB AMEND. |
| TO 2010 FBC SEC. 107.2.1. |
| 5) SUBMIT A WATER RISER FOR REVIEW. SHOW ALL PIPE SIZES |
| AND VALVES. |
| 6) A CLEANOUT IS REQUIRED IN THE STACK FOR THE AIR |
| ADMITTANCE VALVE. FPC SEC.708.3.4. |
| 7) SHOW REQUIREMENTS FOR CONTROLLING THERMAL EXPANSION |
| IN THE WATER SUPPLY SYSTEM PER THE 2010 FPC |
| SEC.607.3.OF THE 2010 FPC. |
| 8) SHOW THE WATER LINES ON THE PLAN VIEW. WPB AMEND. TO |
| 2010 FBC SEC. 107.2.1. |
| 9) ONE OF THE SINKS SHALL COMPLY WITH THE FL. |
| ACCESSIBILITY CODE SEC.212.3, 305, 306, 309 & 606. SHOW |
| THE REQD. CLEAR FLOOR SPACE, HEIGHTS, DIMENSIONS OF |
| SINK, |
| 10) INDICATE ON THE PLAN IF THE WATER HEATER IS BEING |
| INSTALLED ABOVE OR BELOW THE EXISTING COUNTER. IF ABOVE |
| THE CONTER ON A SHELF, A PAN AND PAN DRAIN SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE 2010 FPC SEC.504.7. |
| 11) THE RELIEF LINE SHALL DISCHARGE IN ACCORDANCE WITH |
| 2010 FPC SEC.504.6. |
| |