Plan Review Notes
Plan Review Notes For Permit 15040196
Permit Number 15040196
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-07 06:15:291) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION
 OF THE EXISTING WATER HEATER. WHAT WILL BE DONE WITH
 THE EXISTING PLUMBING AND ELECTRIC? WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 2) INDICATE THE OCCUPANCY OF THIS SPACE? WHAT TYPE OF
 BUSINESS IS CURRENTLY OCCUPYING THIS SPACE? FBC
 SEC.302.
 3) INDICATE ON THE PLANS WHAT THESE SINKS WILL BE USED
 FOR? WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) WHERE IS THE VENT FOR THE EXISTING SINK? WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 5) SUBMIT A WATER RISER FOR REVIEW. SHOW ALL PIPE SIZES
 AND VALVES.
 6) A CLEANOUT IS REQUIRED IN THE STACK FOR THE AIR
 ADMITTANCE VALVE. FPC SEC.708.3.4.
 7) SHOW REQUIREMENTS FOR CONTROLLING THERMAL EXPANSION
 IN THE WATER SUPPLY SYSTEM PER THE 2010 FPC
 SEC.607.3.OF THE 2010 FPC.
 8) SHOW THE WATER LINES ON THE PLAN VIEW. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 9) ONE OF THE SINKS SHALL COMPLY WITH THE FL.
 ACCESSIBILITY CODE SEC.212.3, 305, 306, 309 & 606. SHOW
 THE REQD. CLEAR FLOOR SPACE, HEIGHTS, DIMENSIONS OF
 SINK,
 10) INDICATE ON THE PLAN IF THE WATER HEATER IS BEING
 INSTALLED ABOVE OR BELOW THE EXISTING COUNTER. IF ABOVE
 THE CONTER ON A SHELF, A PAN AND PAN DRAIN SHALL BE
 INSTALLED IN ACCORDANCE WITH THE 2010 FPC SEC.504.7.
 11) THE RELIEF LINE SHALL DISCHARGE IN ACCORDANCE WITH
 2010 FPC SEC.504.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  