2015-05-11 07:59:22 | 5/11/2015 |
| PROJECT: M/M BIKOFSKY |
| PERMIT#: 15040181 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, THE DWELLING UNIT SHALL BE EQUIPPED WITH |
| SMOKE ALARMS AS REQUIRED FOR NEW DWELLINGS. |
| INDICATE THE REQUIRED SMOKE DETECTORS. IF THE REQUIRED |
| SMOKE DETECTORS ARE EXISTING, INDICATE THAT THEY ARE |
| EXISTING TO REMAIN IN LOCATIONS AS REQUIRED BY THE |
| FBC-R 314, AND 315 FOR CARBON MONOXIDE DETECTORS IF |
| |
| 2) FBC-E 502.3.8 RECESSED LIGHTING. |
| RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED AND UNCONDITIONED SPACES. |
| |
| 3) 210.52 (D) BATHROOMS. IN DWELLING UNITS, |
| AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| BASIN. |
| 3A) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL. |
| (A) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL. (1) BATHROOMS |
| 3B) NEC 210.11(C) |
| PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. |
| INDICATE THE REQUIRED 20AMP CIRCUIT AND GFI RECEPTACLES |
| AS INDICATED IN THE NEC 210.52(D), NEC 210.52.8(A)(1) |
| AND NEC 210.11(C). |
| |
| 4) NEC 210.12 |
| ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED. |
| |
| 5) NEC 406.11 |
| ALL NEW GENERAL PURPOSE RECEPTACLES MUST BE TAMPER |
| RESISTANT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |