 PROJECT: M/M BIKOFSKY
 PERMIT#: 15040181
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, THE DWELLING UNIT SHALL BE EQUIPPED WITH
 SMOKE ALARMS AS REQUIRED FOR NEW DWELLINGS.
 INDICATE THE REQUIRED SMOKE DETECTORS. IF THE REQUIRED
 SMOKE DETECTORS ARE EXISTING, INDICATE THAT THEY ARE
 EXISTING TO REMAIN IN LOCATIONS AS REQUIRED BY THE
 FBC-R 314, AND 315 FOR CARBON MONOXIDE DETECTORS IF
  
 2) FBC-E 502.3.8 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES.
  
 3) 210.52 (D) BATHROOMS. IN DWELLING UNITS,
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN.
 3A) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL.
 (A) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. (1) BATHROOMS
 3B) NEC 210.11(C)
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 INDICATE THE REQUIRED 20AMP CIRCUIT AND GFI RECEPTACLES
 AS INDICATED IN THE NEC 210.52(D), NEC 210.52.8(A)(1)
 AND NEC 210.11(C).
  
 4) NEC 210.12
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
  
 5) NEC 406.11
 ALL NEW GENERAL PURPOSE RECEPTACLES MUST BE TAMPER
 RESISTANT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved