Plan Review Notes For Permit 15040162 |
Permit Number |
15040162 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-08 09:18:53 | 1) THE SUBMITTED PLANS SHOW THE TANKLESS WATER HEATER | | LOCATED ON THE INTERIOR OF THE STRUCTUR BUT THE | | SUBMITTED MANUF. SPECIFICATIONS ARE FOR AN OUTDOOR | | MODEL. SUBMIT THE CORRECT SPECIFICATIONS FOR AN INDOOR | | UNIT. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | 2) SHOW THE CAPPED OFF LINE FOR THE UNDERGROUND LINE ON | | THE RISER DIAGRAM. WPB AMEND. TO 2010 FBC SEC.107.2.1, | | 107.3.5.3. | | 3) SIZE THE STEEL LINE TO THE DRYER AND THE TANKLESS | | WATER HEATER ON THE RISER.WPB AMEND. TO 2010 FBC | | SEC.107.2.1. | | 4) INDICATE ON THE PLAN IF THE DRYER IS LOCATED IN A | | CLOSET. IF SO, PROVIDE THE CUBIC FEET OF THE CLOSET. | | COMPLY WITH THE 2010 FGC SEC.614.5.IF LOUVERED DOORS | | ARE ON THE CLOSET, COMPLY WITH THE FGC SEC.304.10 FOR | | THE CALCULATION OF THE NET FREE AREA. | | 5) SUBMIT A VENT DETAIL FOR THE TANKLESS WATER HEATER. | | COMPLY WITH 2010 FGC SEC.502,503.2.3, 503.8 (3). | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|