Date Text
2015-04-08 06:44:181) THE SUBMITTED RINNAI SPECS ARE FOR AN OUTDOOR ONLY
 MODEL AND THE PLANS SHOW THE UNIT INSIDE THE GARAGE.
 SUBMIT COMPLETE MANUF. SPECS FOR AN INDOOR UNIT. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE RANGE AND
 THE DRYER. ALL APPLIANCES SHALL BE LISTED AND LABELED.
 FGC 301.3.
 3)SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATER, DRYER AND RANGE.. COMPLY WITH
 THE 2010 FGC SEC.304.1.
 4) PER TABLE 402.4 (13), THE MAXIMUM ALLOWED BTU LOAD
 FOR 3/4" CSST (EHD 25) IS 97,000 BTU'S AND THE SYSTEM
 LOAD IS 100,000.
 5) SHOW THE SEPARATION WALL BETWEEN THE STRUCTURE AND
 THE GARAGE. AS DRAWN AND LABELED, THE APPLIANCES APPEAR
 TO BE LOCATED IN THE GARAGE..
  