2015-04-06 09:00:54 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. ADVISORY ONLY, PERMIT VALUE WILL BE ADJUSTED TO THE |
| VALUE OF WORK - LABOR, MATERIALS, OVERHEAD, PROFIT, |
| ENGINEERING RATHER THAN THE AMOUNT CONTRACTOR IS BEING |
| PAID TO RESOLVE THE VIOLATION, FBC 109 (HAS BEEN |
| CHANGED TO $20K). |
| |
| 2. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS FOR |
| ALL WINDOWS, FBC EB 604.1. |
| |
| 3. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING |
| INFORMATION FOR BEDROOMS IF WINDOW HEIGHT IS LESS THAN |
| 51?; FBC R310, FBC EB 604.1. THE CLEAR OPENING CANNOT |
| BE REDUCED BY MORE THAN 5%: |
| |
| REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW |
| IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? |
| |
| REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING |
| DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH |
| EXISTS WHEN THE WINDOW IS FULLY OPEN. |
| |
| REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING |
| DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE |
| MANUFACTURER |
| |
| 4. A SLIDING GLASS DOOR PRODUCT APPROVAL WAS SUBMITTED, |
| NONE SHOWN ON THE PLAN, FBC 107. ONE NOA IS FOR A |
| SINGLE HUNG WITH A FIXED WINDOW, NONE SHOWN ON THE |
| PLAN. REVISE PLAN TO SPECIFY LOCATION OF THE PROPOSED |
| ITEMS OR OTHERWISE RESOLVE THE INCONSISTENCY. IF THEY |
| ARE NOT BEING INSTALLED, YOU CAN STATE THIS ON THE |
| RESUBMITTAL FORM AND THE PRODUCT APPROVALS WILL BE |
| REMOVED FOR YOU. |
| |
| 5. DESIGNER OF RECORD TO REVIEW PRODUCT APPROVALS PRIOR |
| TO SUBMITTAL, FBC 107. THIS CAN BE DONE WITH A SHOP |
| DRAWING REVIEW STAMP ON THE PRODUCT APPROVALS, A |
| LETTER, OR BY INCORPORATING THE NOA NUMBERS INTO THE |
| PLAN. |
| |
| 6. APPLICATION IS NOT CONSISTENT WITH PLAN. APPLICATION |
| STATES THAT TWO EXTERIOR DOORS PROPOSED, PLAN SHOWS |
| THREE. DESCRIPTION ON PERMIT HAS BEEN REVISED TO BE |
| CONSTENT WITH THE PLAN. IF THE PLAN IS NOT CORRECT, |
| PLEASE REVISE ACCORDINGLY FBC 107. |
| |
| 7. AS THIS PARCEL IS LOCATED IN A HISTORIC DISTRICT, |
| HISTORIC REVIEW REQUIRED. PRIOR TO ISSUANCE, ALL |
| PRODUCT APPROVALS ARE TO BE APPROVED BY THE HISTORIC |
| PRESERVATION DEPARTMENT, CITY OF WEST PALM BEACH |
| MUNICIPAL CODE 94-46. |
| |
| |
| |